Analog modules
5.20 Analog input module SM 431; AI 8 x 14 Bit (6ES7431-1KF10-0AB0)
Measuring ranges
Set the measuring ranges using the measuring range modules, and at the "measuring method"
parameter in
Table 5-52
Measuring ranges of the SM 431; AI 8 x 14 Bit (6ES7431-1KF10-0AB0)
Selected measuring method
V: Voltage
2DMU: Current
(2-wire transducer)
4DMU: Current
(4-wire transducer)
R-4L: Resistance
(4-conductor connection)
R-3L: Resistance
(3-conductor connection)
252
STEP 7 .
Measuring range
(type of sensor)
± 80 mV
± 250 mV
± 500 mV
± 1 V
± 2.5 V
± 5 V
1 to 5 V
± 10 V
4 to 20 mA
0 mA to 20 mA
4 mA to 20 mA
± 20 mA
48 Ω
150 Ω
300 Ω
600 Ω
6000 Ω
300 Ω
600 Ω
6000 Ω
Measuring range module
settings
A
D
C
A
Reference Manual, Ausgabe 11/2016, A5E00850736-08
Description
The digitized analog values are lis‐
ted in the section "Representation
of analog values for analog input
channels" in the voltage measur‐
ing range.
To supply these transducers with
current you must connect 24 V to
the L+ and M front connector ter‐
minals.
The digitized analog values are lis‐
ted in the section "Representation
of analog values for analog input
channels" in the current measur‐
ing range.
The digitized analog values are lis‐
ted in the section "Representation
of analog values for analog input
channels" in the current measur‐
ing range.
The digitized analog values are lis‐
ted in the section "Representation
of analog values for analog input
channels" in the resistance meas‐
uring range.