Interface Modules; Common Features Of The Interface Modules - Siemens SIMATIC S7-400 Reference Manual

Automation system module data
Hide thumbs Also See for SIMATIC S7-400:
Table of Contents

Advertisement

Interface modules

6.1

Common features of the interface modules

Function
Interface modules (a send IM and a receive IM) are required if one or more expansion racks
(ER) are to be connected to a central rack (CR). This configuration is described in the
Installation manual .
Configuration
Interface modules must always be used together. The send modules (send IMs) are inserted
in the CR, whilst the corresponding receive modules (receive IMs) are plugged into the series-
connected ER.
Table 6-1
IM 460-0
IM 461-0
IM 460-1
IM 461-1
IM 460-3
IM 461-3
IM 460-4
IM 461-4
Overview of the connections
Note the rules for connections in the section after next.
Table 6-2
Send IM
Receive IM
Max. number of connectable EMs per line
Max. distance
V transfer
Max. current transfer per interface
Communication bus transmission
S7-400 Automation System Module Data
Reference Manual, Ausgabe 11/2016, A5E00850736-08
Interface modules of the S7-400
Partner
Send IM for local link without PS transfer; with communication bus
Receive IM for local link without PS transfer; with communication bus
Send IM for local link with PS transfer; without communication bus
Receive IM for local link with PS transfer; without communication bus
Send IM for remote link up to 102.25 m; with communication bus
Receive IM for remote link up to 102.25 m; with communication bus
Send IM for remote link up to 605 m; without communication bus
Receive IM for remote link up to 605 m; without communication bus
Overview of the connections
Areas of application
Local connection
460-0
460-1
461-0
461-1
4
1
5 m
1.5 m
No
Yes
-
5 A
Yes
No
6
Remote connection
460-3
460-4
461-3
461-4
4
4
102.25 m
605 m
No
No
-
-
Yes
No
325

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents