Measuring Methods And Measuring Ranges Of Sm 431; Ai 16 X 13 Bit - Siemens SIMATIC S7-400 Reference Manual

Automation system module data
Hide thumbs Also See for SIMATIC S7-400:
Table of Contents

Advertisement

5.22.3

Measuring methods and measuring ranges of SM 431; AI 16 x 13 Bit

Measuring methods
You can set the measuring method at the input channels:
● Voltage measurement
● Current measurement
You specify the setting by means of the measuring range modules on the module and the
"Measuring type" parameter in STEP 7.
Circuit variants for the channels
Two channels are set in each case with the measuring range module. There are therefore
restrictions as regards the measuring method for the adjacent channels 0/1, 2/3, 4/5, 6/7, 8/9,
10/11, 12/13 and 14/15, as shown in the following table:
Table 5-59
Selection of the measuring method for channel n and channel n+1 of the SM 431; AI 16 x 13 Bit
Measuring method, chan‐
nel n
Disabled
Voltage ±1 V
Voltage 1 to 5 V
Voltage ±10 V
Current 4-wire transducer
Current 2-wire transducer
Example
If you select "current (2-wire transducer)" for channel 6, you can only disable the measuring
method or set "current (2-wire transducer)" for channel 7.
Unused channels
Unused channels can be left open. Set the measuring range modules to position "B". You can
improve the noise immunity of the module in a measuring environment with serious
interference by interconnecting M- and M
For unused channels, set the "measuring method" parameter to "deactivated". This reduces
the module's cycle time.
S7-400 Automation System Module Data
Reference Manual, Ausgabe 11/2016, A5E00850736-08
5.22 Analog input module SM 431; AI 16 x 13 Bit (6ES7431-0HH00-0AB0)
Disabled
Voltage
±1 V
x
x
x
x
x
x
x
x
Measuring method, channel n + 1
Voltage 1 to 5
Voltage ±10 V
V
x
x
x
x
x
x
.
ANA
Analog modules
Current 4-
Current 2-
DMU
DMU
x
x
x
x
271

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents