Active Setpoint; Active Setpoint (Si); Capacity Control Algorithms; Supply Air Temperature Control - Carrier 38APS025 Manual

Gemini select, commercial air-cooled condensing units with comfortlink version 6.x controls 50/60 hz
Table of Contents

Advertisement

90
80
70
60
50
40
30
20
10
30.0
25.0
20.0
15.0
10.0
CAPACITY CONTROL ALGORITHMS — Three types of
capacity control are available for the 38AP units.
Supply Air Temperature Control — This control algorithm is
applicable to Control Types Configuration OPT2
C.TYP=1 (VAV), 3 (Tstat Multi), 5 (SPT Multi), or 9 (VAV
Setpoint).
Capacity control is determined by the difference between
the supply air temperature and the Control Point (Run Sta-
tus VIEW CTPT) and its rate of change. The capacity con-
trol routine runs every 30 seconds. The algorithm attempts to
maintain the Control Point at the desired set point. Additional-
ly, the control calculates a rise per stage knowing which com-
pressor is on, its capacity and the temperature difference across
the evaporator coil (return or mixed air temperature minus sup-
ply air temperature) to determine the best time to turn on or off
the next compressor, institute Minimum Load Control, or
change the digital response, if equipped. Supply and return air
temperatures can be monitored at the unit's interface device
0
0
5
CL.MA (4-20 mA COOLING SETPOINT INPUT), mA
Fig. 142 — Active Setpoint (English)
5.0
0.0
0
5
CL.MA (4-20 mA COOLING SETPOINT INPUT), mA
Fig. 143 — Active Setpoint (SI)
10
15
10
15
Return Air Temperature Temperatures UNIT RAT and
Supply Air Temperature Temperatures UNIT SAT. With
this information, a capacity ratio is calculated to determine
whether to make any changes to the current stage of capacity.
This ratio, Capacity Load/Unload Factor (Run Sta-
tus VIEW LOD.F) value ranges from –100% to +100%
times Deadband Multiplier (Configuration SLCT Z.GN).
See Deadband Multiplier on page 115 for more information. If
the next stage of capacity is a compressor, the control starts
(stops) a compressor when the ratio reaches +100% (–100%)
times Deadband Multiplier (Z.GN). Once a change in capacity
occurs, a 90-second time delay is initiated and the capacity
stage is held during this time delay.
When the unit is at stage zero (Requested Stage Run Sta-
tus VIEW STGE=0) as part of the capacity control routine,
the control adds a 1.2 factor on adding the first stage to reduce
cycling.
110
20
25
a38-7285
20
25
a38-7286

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents