Carrier 38APS025 Manual page 183

Gemini select, commercial air-cooled condensing units with comfortlink version 6.x controls 50/60 hz
Table of Contents

Advertisement

Configuration Mode and Sub-Mode Directory (cont)
SUB-MODE
CSB.E
SP.O.S
SP.O.R
OPT1
C.TYP
OPT2
APPENDIX A — DISPLAY TABLES (cont)
ITEM
DISPLAY
MLV.S
YES/NO
ENBL/DSBL
SPT.S
ENBL/DSBL
ENBL/DSBL
XX F ( C)
RAT.T
X
SAT.T
X
EMM
YES/NO
X
CTRL
X
LOAD
X
LLCS
X
DELY
XX MIN
ITEM DESCRIPTION
UNIT OPTIONS 1 HARDWARE
Minimum Load Valve Select
CSB Boards Enable
Space Temp Sensor
Space Temp Offset Enable
Space Temp Offset Range
RAT Thermistor Type
SAT Thermistor Type
EMM Module installed
UNIT OPTIONS 2 CONTROLS
Machine Control Type
Control Method
Loading Sequence Select
Lead/Lag Circuit Select
Minutes Off Time
183
COMMENT
Default:
YES = Factory Equipped
NO = Not Equipped
Default: ENBL
Default: DSBL
Default: DSBL
Range: 1 to 10 F (0.6 to 5.6 C)
Default: 5 F (2.8 C)
Range 0 to 2
0 = 5 k
1 = 10 k
2 = None
Default: 0
Range 0 to 2
0 = 5 k
1 = 10 k
2 = None
Default: 0
Default:
YES = Factory Equipped
NO = Not Equipped
Range: 1 to 9
1 = VAV
2 = Invalid
3 = Tstat Multi
4 = Tstat 2 Stg
5 = SPT Multi
6 = Invalid
7 = Pct Cap
8 = Dual Tstat
9 = VAV Setpoint
Default: 4
Range: 0 to 3
0 = Switch
1 = Occupancy
2 = Occupancy
3 = CCN Control
Default: 0
Range: 1 to 2
1 = Equal
2 = Staged
Default: 1
Range: 1 to 3
1 = Automatic
2 = Circuit A Leads
3 = Circuit B Leads
Default: 1
Range: 0 to 15 Minutes
Default: 0