Time Required Configuration; Day And Date Required Configurations; Broadcast Required Configurations; Daylight Savings Required Configurations - Carrier 38APS025 Manual

Gemini select, commercial air-cooled condensing units with comfortlink version 6.x controls 50/60 hz
Table of Contents

Advertisement

SUBMODE
TIME
SUBMODE
DATE
SUBMODE
BCST
*Only the time and date broadcaster can perform daylight savings
time adjustments. Even if the unit is stand-alone, the user may want
to set this to ON to accomplish the daylight savings function.
SUBMODE
DST
BCST
This term refers to how the
Control Methods —
machine is started and stopped. Several control methods are
available to enable and disable the unit. Machine On/Off con-
trol is determined by the configuration of the Control Method,
Configuration OPT2 CTRL.
ENABLE-OFF-REMOTE CONTROL — With the control
method set to Enable-Off-Remote Contact, CTRL=0 (Switch) ,
simply switching the Enable/Off/Remote Control switch to the
Table 16 — Time Required Configuration
ITEM
DISPLAY
HH.MM
Table 17 — Day and Date Required Configurations
ITEM
DISPLAY
MNTH
DOM
DAY
YEAR
XXXX
Table 18 — Broadcast Required Configurations
CONFIGURATION MODE
ITEM
DISPLAY
T.D.BC
ON/OFF
BC.AK
ON/OFF
Table 19 — Daylight Savings Required Configurations
TIME CLOCK MODE
ITEM
DISPLAY
STR.M
XX
STR.W
X
STR.D
X
MIN.A
XX
STP.M
XX
STP.W
X
STP.D
X
MIN.S
XX
CONFIGURATION MODE
T.D.BC
ON/OFF
TIME CLOCK MODE
ITEM DESCRIPTION
XX.XX
Hour and Minute
TIME CLOCK MODE
ITEM DESCRIPTION
XX
Month of Year
XX
Day of Month
X
Day of Week
Year of Century
ITEM DESCRIPTION
CCN Time/Date Broadcast
CCN Broadcast Ack'er
ITEM DESCRIPTION
Month
Week
Day
Minutes to Add
Month
Week
Day
Minutes to Subtract
CCN Time/Date Broadcast
Enable or Remote Control position with external contacts
closed will place the unit in an occupied state.
Under normal operation, the Control Mode (Run Sta-
tus VIEW STAT ) will be 1 (Off Local) when the switch is
in the Off position or in the Remote Control position with ex-
ternal contacts open, and will be 5 (On Local) when in the En-
able position or Remote Control position with external contacts
closed. If the machine is ON, the Control Type Configura-
tion OPT2 C.TYP=5 (SPT Multi) is used, and the space
60
COMMENT
24-hour format
Range: 00.00 to 23.59
COMMENT
Range: 1-12
(1=January, 2=February, etc.)
Range: 1-31
Range: 1-7
(1=Monday, 2=Tuesday, etc.)
COMMENT
Default: Off
Must be set to ON to enable automatic
Daylight Savings Time correction.*
Default: Off
One unit on the network must be set to
ON. The broadcast unit cannot be the
acknowledger.
COMMENT
Daylight Savings Start Month
Default: 4 (April)
Range: 1 to 12
(1=January, 2=February, etc.)
Daylight Savings Start Week
Default: 1
Range: 1 to 5
Daylight Savings Start Day
Default: 7 (Sunday)
Range: 1 to 7
(1=Monday, 2=Tuesday, etc.)
Default: 60
Range: 0 to 99
Daylight Savings Stop Month
Default: 10 (October)
Range: 1 to 12
(1=January, 2=February, etc.)
Daylight Savings Stop Week
Default: 5
Range: 1 to 5
Daylight Savings Stop Day
Default: 7 (Sunday)
Range: 1 to 7
(1=Monday, 2=Tuesday, etc.)
Default: 60
Range: 0 to 99
Default: Off
Must be set to ON to enable automatic
Daylight Savings Time correction.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents