Carrier Gemini 38AU 16-28 Series Installation, Start-Up And Service Instructions Manual

Carrier Gemini 38AU 16-28 Series Installation, Start-Up And Service Instructions Manual

Air-cooled condensing units with puron (r-410a) refrigerant

Advertisement

Quick Links

Installation, Start-Up and Service Instructions
CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1
INSTALLATION GUIDELINES . . . . . . . . . . . . . . . . . . . 2
R-22 to Puron Refrigerant . . . . . . . . . . . . . . . . . . . 2
Rated Indoor Airflow (cfm) . . . . . . . . . . . . . . . . . . . . . 2
Identify Factory Options . . . . . . . . . . . . . . . . . . . . . . . 3
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Jobsite Survey . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Step 1 - Plan for Unit Location . . . . . . . . . . . . . . . . 7
Step 4 - Rig and Mount the Unit . . . . . . . . . . . . . . . 7
Suction Riser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Step 7 - Install Accessories . . . . . . . . . . . . . . . . . . 14
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
System Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Turn On Crankcase Heater . . . . . . . . . . . . . . . . . . . . 20
Preliminary Charge . . . . . . . . . . . . . . . . . . . . . . . . . . 20
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Start Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
OPERATING SEQUENCE . . . . . . . . . . . . . . . . . . . . . 27
Base Unit Controls . . . . . . . . . . . . . . . . . . . . . . . . . . 27
All Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
(and 30 days after initial start) . . . . . . . . . . . . . . . 27
Seasonal Maintenance . . . . . . . . . . . . . . . . . . . . . . . 28
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Refrigeration System . . . . . . . . . . . . . . . . . . . . . . . . 28
Comfort Alert Diagnostic Module . . . . . . . . . . . . . . 29
Compressor Protection . . . . . . . . . . . . . . . . . . . . . . 35
Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Fastener Torque Values . . . . . . . . . . . . . . . . . . . . . . 36
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . 36
®
APPENDIX B - WIRING DIAGRAMS . . . . . . . . . . . . 39
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53380046-01
Page
Printed in U.S.A.
Form 38AU-16-28-01SI
Air-Cooled Condensing Units
with Puron
(R-410A) Refrigerant
®
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . .CL-1

SAFETY CONSIDERATIONS

Improper
installation,
maintenance, or use can cause explosion, fire, electrical shock or
other conditions which may cause personal injury or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory-authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses and work gloves. Use
quenching cloths for brazing operations and have a fire
extinguisher available. Read these instructions thoroughly and
follow all warnings or cautions attached to the unit. Consult local
building codes and appropriate national electrical codes (in
U.S.A., ANSI/NFPA70, National Electrical Code (NEC); in
Canada, CSA C22.1) for special requirements.
It is important to recognize safety information. This is the safety-
alert symbol
. When you see this symbol on the unit and in
instructions or manuals, be alert to the potential for personal
injury.
Understand the signal words DANGER, WARNING, CAUTION,
and NOTE. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies hazards
which could result in personal injury or death. CAUTION is used
to identify unsafe practices, which may result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability,
or operation.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning will result in personal injury or
death.
Before performing service or maintenance operations on unit,
turn off main power switch to unit and install lock(s) and
lockout tag(s). Ensure electrical service to rooftop unit agrees
with voltage and amperage listed on the unit rating plate. Unit
may have more than one power switch.
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal injury,
death and/or equipment damage.
R-410A refrigerant systems operate at higher pressures than
standard R-22 systems. Do not use R-22 service equipment or
components on R-410A refrigerant equipment.
Pg 1
Gemini™
38AU**16-28
adjustment,
alteration,
DANGER
1-23
Replaces: 38AU-16-25-01SI
service,

Advertisement

Table of Contents
loading

Summary of Contents for Carrier Gemini 38AU 16-28 Series

  • Page 1: Table Of Contents

    Gemini™ 38AU**16-28 Air-Cooled Condensing Units with Puron (R-410A) Refrigerant ® Installation, Start-Up and Service Instructions CONTENTS START-UP CHECKLIST .....CL-1 Page SAFETY CONSIDERATIONS SAFETY CONSIDERATIONS .
  • Page 2: Installation Guidelines

    typically oversized for Puron applications. Carefully check the existing suction line size against the table for maximum size; WARNING replace vertical riser segments if necessary. Check existing liq- uid line size against sizing data in Tables 7 and 8 or; replace PERSONAL INJURY AND ENVIRONMENTAL...
  • Page 3: Identify Factory Options

    10 11 12 13 14 15 16 17 18 3 8 A U D T 2 5 A 0 A 6 – 0 A 0 A 0 Model Type Packaging 38AU = Carrier Condensing Unit 0 = Standard Puron ®...
  • Page 4 Fig. 3 — 38AUD/Z 16 Base Unit Dimensions...
  • Page 5 Fig. 4 — 38AUZ 25 / 38AUD 25-28 Base Unit Dimensions...
  • Page 6 Table 4 — 38AUZ*16-25 Physical Data UNIT 38AUZ(A,B)16 38AUZ(A,B)25 NOMINAL CAPACITY (TONS) OPERATING WEIGHT (LB) REFRIGERATION SYSTEM # Circuits / # Comp. / Type 1 / 2 / Scroll 1 / 2 / Scroll Refrigerant Type R-410A R-410A R-410A Shipping Charge A/B (lb) System Charge w/ Fan Coil 43.0 38.0...
  • Page 7: Installation

    INSTALLATION UN-CRATE UNIT Remove unit packaging except for the top skid assembly, which Jobsite Survey should be left in place until after the unit is rigged into its final Complete the following checks before installation. location. Consult local building codes and the NEC (National Electrical INSPECT SHIPMENT Code) ANSI/NFPA 70 for special installation requirements.
  • Page 8 Refer to Part 3 of the A liquid lift condition exists when the outdoor unit is located be- Carrier System Design Manual for additional data and information low the indoor (evaporator) unit and liquid flows vertically up in a on equivalent lengths.
  • Page 9 Table 7 — 38AUZ_16-25 Piping Recommendations (Single-Circuit) MODEL & LINEAR LINE (FT) 0 - 24 25 - 49 50 - 74 75 - 99 100 - 124 125 - 149 150 - 174 175 - 200 NOMINAL EQUIV. LINE (FT) 0 - 37 38 - 74 75 - 112...
  • Page 10 Table 8 — 38AUD_16-28 Piping Recommendations (Dual-Circuit) MODEL & LINEAR LINE (FT) 0 - 24 25 - 49 50 - 74 75 - 99 100 - 124 125 - 149 150 - 174 175 - 200 NOMINAL EQUIV. LINE (FT) 0 - 37 38 - 74 75 - 112...
  • Page 11: Suction Riser

    Suction Riser A suction riser condition exists when the outdoor unit is located above the indoor (evaporator) unit and suction vapor must flow vertically up to return to the compressor. Oil return is a concern when the suction tube size is too large to produce the minimum re- frigerant velocity to ensure oil return at minimum load conditions.
  • Page 12 Vertical Installation Liquid Line Connection Suction-Vapor Connection Coil Segment 1 Circuit 2 Condensate Drain Connections Connection Circuit 1 Coil Segment 2 First On/Last Off = 2 Connections Horizontal Installation Fig. 8 — 38AUD Service Valve Locations When a single piece evaporator coil with two separate circuits is connected to a 38AUD, the lower coil circuit should be connected to the 38AUD unit’s Circuit 1 so that the evaporator’s lower coil segment is first-on/last-off (to avoid re-evaporation of condensate...
  • Page 13 In some applications, depending on space and convenience re- EQUALIZER LINE quirements, it may be desirable to install 2 filter driers and sight glasses in a single circuit application. One filter drier and SENSING BULB sight glass may be installed at A locations (see Fig. 10) or 2 fil- ter driers and sight glasses may be installed at B locations (see AIRFLOW Fig.
  • Page 14: Step 7 - Install Accessories

    For linear line lengths longer than 125 ft (38 m), contact your local R-410A refrigerant systems operate at higher pressures than Carrier representative for system charge value. standard R-22 systems. Do not use R-22 service equipment or components on R-410A refrigerant equipment.
  • Page 15: Step 8 - Complete Electrical Connections

    Step 8 — Complete Electrical Connections UNITS WITH FACTORY-INSTALLED NON-FUSED DISCONNECT The factory-installed option disconnect switch is located in a WARNING weatherproof enclosure located under the main control box. The manual switch handle is accessible through an opening in the ac- ELECTRIC SHOCK HAZARD cess panel.
  • Page 16 CONVENIENCE OUTLETS WARNING ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or death. Units with convenience outlet circuits may use multiple disconnects. Check convenience outlet for power status before opening unit for service. Locate its disconnect switch, if appropriate, and open it.
  • Page 17 (air handler or packaged fan coil). Figures 18 (38AUZ) and 19 (38AUD) depict typical connections to a Carrier 40RU fan coil unit. Plan for field connections carefully and install control wir- ing correctly per the project plan.
  • Page 18 The 38AUD is a dual-circuit, three-stage cooling unit. Select a three-stage cooling thermostat, with or without supplemental heat- ing as needed. Select a thermostat cable or equivalent single leads of different colors with minimum of five leads for 38AUZ or six leads for 38AUD unit.
  • Page 19 Table 13 — 38AUZ Unit Wire/Fuse or HACR Breaker Sizing Data NOMINAL COMPRESSOR NO C.O. OR PWRD C.O. VOLTAGE POWER RANGE UNIT NUMBER No. 1 No. 2 Power Supply Disconnect Size SUPPLY SIZE Fuse or 38AUZ STAGES V-Ph-Hz HACR (ea) Breaker 208/230 25.0...
  • Page 20: Step 9 - Wind Baffles For Low Ambient Control

    Legend and Notes for Tables 13-14 PRE-START-UP LEGEND IMPORTANT: Before beginning Pre-Start-Up or Start-Up, — Full Load Amps review Start-Up Checklist at the back of this book. The Check- — Locked Rotor Amps list assures proper start-up of a unit and provides a record of MOCP —...
  • Page 21: Start-Up

    Refer to Cooling Charging Charts, Fig. 24-28. For applications separate, which stops compression. Suction and discharge with line lengths greater than 125 ft (38 m), contact Carrier repre- pressures balance while the motor continues to run. The longer sentative. Make sure that all condenser fans are operating before adjusting charge to the charging charts.
  • Page 22 charging the units to the correct subcooling for the various operat- ing conditions. Accurate pressure gage and temperature sensing device are required. Connect the pressure gage to the service port on the liquid line service valve. Mount the temperature sensing de- vice on the liquid line close to the liquid line service valve, and in- sulate it so that outdoor ambient temperature does not affect the reading.
  • Page 23 20 Ton Charging Chart R-410A Refrigerant Add Charge if Above the Curve Remove Charge if Below the Curve 1050 1400 1750 2100 2450 2800 3150 3500 3850 Pressure at Liquid Valve (PSIG / kPa) 38AU500733 Fig. 25 — 38AUZ*25 Charging Chart...
  • Page 24 15 Ton Circuit A Charging Chart R-410A Refrigerant 15 Ton Circuit B Charging Chart R-410A Refrigerant Add Charge if Add Charge if Above the Curve Above the Curve Remove Charge if Rem ove Charge if Below the Curve Below the Curve 100 150 200 250 300 350 400 450 500 550 600 100 150 200 250 300 350 400 450 500 550 600 350 700 1050 1400 1750 2100 2450 2800 3150 3500 3850...
  • Page 25 20 Ton Circuit A Charging Chart R-410A Refrigerant 20 Ton Circuit B Charging Chart R-410A Refrigerant Add Charge if Add Charge if Above the Curve Above the Curve Remove Charge if Remove Charge if Below the Curve Below the Curve 100 150 200 250 300 350 400 450 500 550 600 100 150 200 250 300 350 400 450 500 550 600 350 700 1050 1400 1750 2100 2450 2800 3150 3500 3850...
  • Page 26 25 Tons Circuit A R-410A CHARGING CHART 25 Tons Circuit B R-410A CHARGING CHART 59.9 59.9 48.8 48.8 Add Charge if Above the Curve Add Charge if Above the Curve 37.7 37.7 26.6 26.6 15.5 15.5 Remove Charge if Below the Curve Remove Charge if Below the Curve -6.7 -6.7...
  • Page 27: Operating Sequence

    OPERATING SEQUENCE received at CADM1 terminal Y2. CADM1 DC SOL terminal out- puts 24-vdc to the compressor loader plug (LDR) and the Com- Base Unit Controls pressor 1 operates at full load capacity. As space cooling load is satisfied, thermostat outputs Y3, Y2 and INDOOR (SUPPLY) FAN Y1 are de-energized, removing 24-v at 38AUD terminals X (Y3), If the thermostat fan operation is selected as Continuous the in-...
  • Page 28: Seasonal Maintenance

    The above list may not include all maintenance items. Inspection intervals may See Tables 16 and 17 for unit specific maintenance checklists. vary depending on climate and opening hours. Consult your Carrier dealer about a service contact for seasonal inspections b.
  • Page 29: Comfort Alert Diagnostic Module

    appropriate precautions to protect roofing. Procedures which risk The CADM detects causes for electrical and system related fail- oil leakage include but are not limited to compressor replacement, ures without any sensors. Flashing LEDs communicate the Alert repairing refrigerants leaks, replacing refrigerant components such codes to guide service technicians in accurately and quickly trou- as filter drier, pressure switch, metering device, coil, accumulator, bleshooting the system and determining root cause for the failure.
  • Page 30 Simultaneous blinking of YELLOW and RED LEDs indicates control power input to the CADM is low. Check control circuit transformer and wiring. Condenser Fans/Motors Outdoor Fan 1 Outdoor Fan 2 Outdoor Fan 3 Access Panel - Control Box and Compressors Service Valves Fig.
  • Page 31 Suction Equalizer Oil Equalizer Line Fig. 32 — 38AUZ*16 Compressor Assembly (Rear View) Fig. 33 — 38AUD*16 Compressor Assembly (Rear View)
  • Page 32 Condenser Fans/Motors Outdoor Outdoor Fan 1 Fan 4 Outdoor Fan 2 Outdoor Fan 3 Access Panel - Control Box & Compressors Service Valves Fig. 34 — 38AUZ,D Size 25 Cabinet Fig. 35 — 38AUD*25 Piping...
  • Page 33 Fig. 36 — 38AUZ*25 Compressor Assembly (Rear View) Fig. 37 — 38AUD*25 Compressor Assembly (Rear View)
  • Page 34 TROUBLESHOOTING THE CADM WIRING Flashing LEDs also indicate wiring problems to the CADM. See Tables 19 and 20 for discussion of additional LED flash codes and troubleshooting instructions. Table 19 — LED Status Codes STATUS LED STATUS LED DESCRIPTION STATUS LED TROUBLESHOOTING INFORMATION Green “POWER”...
  • Page 35: Compressor Protection

    RTPF coils. This cleaner is See “Advanced Scroll Temperature Protection (ASTP)” on available from Carrier Replacement parts division as part number page 21. P902-0301 for a one gallon container, and part number P902-0305 LOW-PRESSURE SWITCH for a 5 gallon container.
  • Page 36: Fastener Torque Values

    TOTALINE ENVIRONMENTALLY BALANCED COIL applied in the direction of the fins. Coil surfaces can be easily CLEANER APPLICATION EQUIPMENT damaged (fin edges can be easily bent over and damage to the coating of a protected coil) if the tool is applied across the •...
  • Page 37 Table 22 — Troubleshooting PROBLEM SOLUTION COMPRESSOR DOES NOT RUN Contactor Open 1. Power off. 1. Restore power. 2. Fuses blown in field power circuit. 2. After finding cause and correcting, replace with correct size fuse. 3. No control power. 3.
  • Page 38: Appendix A - Air Conditioner And Heat Pump With Puron ® - Quick Reference Guide

    Table 22 — Troubleshooting (cont) PROBLEM SOLUTION UNIT OPERATES TOO LONG OR CONTINUOUSLY 1. Low refrigerant charge. 1. Add refrigerant. 2. Control contacts fused. 2. Replace control. 3. Air in system. 3. Purge and evacuate system. 4. Partially plugged expansion valve or filter drier. 4.
  • Page 39: Appendix B - Wiring Diagrams

    APPENDIX B — WIRING DIAGRAMS ELECTRICAL UNIT DIAGRAM NUMBER PAGE NUMBER CHARACTERISTICS 208/230-3-60 38AU501341 38AUD*16 460-3-60 38AU501340 575-3-60 38AU501342 208/230-3-60 38AU501337 38AUD*25 460-3-60 38AU501336 575-3-60 38AU501338 208/230-3-60 38AU501345 38AUD*28 460-3-60 38AU501344 575-3-60 38AU501346 208/230-3-60 38AU500537 38AUZ*16 460-3-60 38AU500538 575-3-60 38AU500539 208/230-3-60 38AU500568 38AUZ*25...
  • Page 40 APPENDIX B — WIRING DIAGRAMS (CONT) Fig. A — Dual Circuit/Three Stage Wiring Diagram, 15 Ton — 208/230-3-60 Unit...
  • Page 41 APPENDIX B — WIRING DIAGRAMS (CONT) Fig. B — Dual Circuit/Thee Stage Wiring Diagram, 15 Ton — 460-3-60 Unit...
  • Page 42 APPENDIX B — WIRING DIAGRAMS (CONT) Fig. C — Dual Circuit/Three Stage Wiring Diagram, 15 Ton — 575-3-60 Unit...
  • Page 43 APPENDIX B — WIRING DIAGRAMS (CONT) Fig. D — Dual Circuit/Three Stage Wiring Diagram, 20 Ton — 208/230-3-60 Unit...
  • Page 44 APPENDIX B — WIRING DIAGRAMS (CONT) Fig. E — Dual Circuit/Thee Stage Wiring Diagram, 20 Ton — 460-3-60 Unit...
  • Page 45 APPENDIX B — WIRING DIAGRAMS (CONT) Fig. F — Dual Circuit/Three Stage Wiring Diagram, 20 Ton — 575-3-60 Unit...
  • Page 46 APPENDIX B — WIRING DIAGRAMS (CONT) Fig. G — Dual Circuit/Three Stage Wiring Diagram, 25 Ton — 208/230-3-60 Unit...
  • Page 47 APPENDIX B — WIRING DIAGRAMS (CONT) Fig. H — Dual Circuit/Three Stage Wiring Diagram, 25 Ton — 460-3-60 Unit...
  • Page 48 APPENDIX B — WIRING DIAGRAMS (CONT) Fig. I — Dual Circuit/Three Stage Wiring Diagram, 25 Ton — 575-3-60 Unit...
  • Page 49 APPENDIX B — WIRING DIAGRAMS (CONT) Fig. J — Single Circuit/Two Stage Wiring Diagram, 15 Ton — 208/230-3-60 Unit...
  • Page 50 APPENDIX B — WIRING DIAGRAMS (CONT) Fig. K — Single Circuit/Two Stage Wiring Diagram, 15 Ton — 460-3-60 Unit...
  • Page 51 APPENDIX B — WIRING DIAGRAMS (CONT) Fig. L — Single Circuit/Two Stage Wiring Diagram, 15 Ton — 575-3-60 Unit...
  • Page 52 APPENDIX B — WIRING DIAGRAMS (CONT) Fig. M — Single Circuit/Two Stage Wiring Diagram, 20 Ton — 208/230-3-60 Unit...
  • Page 53 APPENDIX B — WIRING DIAGRAMS (CONT) Fig. N — Single Circuit/Two Stage Wiring Diagram, 20 Ton — 460-3-60 Unit...
  • Page 54 APPENDIX B — WIRING DIAGRAMS (CONT) Fig. O — Single Circuit/Two Stage Wiring Diagram, 20 Ton — 575-3-60 Unit...
  • Page 55: Appendix C - Low Ambient Option

    APPENDIX C — LOW AMBIENT OPTION Units with the factory installed low ambient option are equipped Troubleshooting with a solid-state head pressure control which regulates fan speed. OBSERVATION POSSIBLE REMEDY A temperature sensor, mounted on either circuit 1 (38AUZ units) or both circuits 1 and 2 (38AUD units) of the outdoor coil controls All fans: Check power and wiring...
  • Page 56 APPENDIX C — LOW AMBIENT OPTION (CONT) Low Ambient Sensor 2 Must Be Positioned On Vapor Stub Low Ambient Sensor 1 Must Be Positioned On Vapor Stub Circuit 2 Circuit 1 Fig. P — 38AUD*16 Low Ambient Sensor Locations Low Ambient Sensor 2 Must Be Positioned On Vapor Stub (Fourth From Top)
  • Page 57 ® Motormaster Sensor Must Be Positioned On Vapor Stub Fig. R — 38AUZ*16/25 Low Ambient Sensor Location Table A — Wind Baffle Dimension DIMENSIONS (in.) UNIT BAFFLE LEFT SIDE 10-3/4 11-1/2 12-1/4 43-1/8 4-1/4 13-1/4 22-1/4 31-1/4 40-1/4 BACK 80-1/4 81-3/4 43-1/8 8-3/8...
  • Page 58 APPENDIX C — LOW AMBIENT OPTION (CONT) Fig. S — Wind Baffles – Fabrication...
  • Page 59 APPENDIX C — LOW AMBIENT OPTION (CONT) Fig. T — 15 Ton Wind Baffle Brackets – Fabrication...
  • Page 60 APPENDIX C — LOW AMBIENT OPTION (CONT) TOP BRACKETS FRONT BOTTOM BRACKET BACK LEFT RIGHT Fig. U — Wind Baffle Installation – 15 Ton Units...
  • Page 61 APPENDIX C — LOW AMBIENT OPTION (CONT) FRONT LEFT BACK RIGHT Fig. V — Wind Baffle Installation – 20 and 25 Ton Units...
  • Page 62 © 2023 Carrier Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53380046-01 Printed in U.S.A. Form 38AU-16-28-01SI Pg 62 1-23 Replaces: 38AU-16-25-01SI...
  • Page 63: Start-Up Checklist

    START-UP CHECKLIST (Remove and use for Job File) NOTE: To avoid injury to personnel and damage to equipment or property when completing the procedures listed in this start-up checklist, use good judgment, follow safe practices, and adhere to the safety considerations/information as outlined in preceding sections of this Installation, Start-Up, and Service document.
  • Page 64 ________________________________________________________________________________________________________ ________________________________________________________________________________________________________ ________________________________________________________________________________________________________ ________________________________________________________________________________________________________ ________________________________________________________________________________________________________ ________________________________________________________________________________________________________ © 2023 Carrier Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53380046-01 Printed in U.S.A. Form 38AU-16-28-01SI Pg CL-2 1-23...