SUB-MODE
GEN.I
CRCT
4-20
SUB-MODE
GEN.O
CIR.A
CIR.B
APPENDIX A — DISPLAY TABLES (cont)

Inputs Mode and Sub-Mode Directory

ITEM
DISPLAY
STST
STRT/STOP
ID.F.A
ON/OFF
Y.1
ON/OFF
Y.2
ON/OFF
ID.F.B
ON/OFF
Y.3
ON/OFF
Y.4
ON/OFF
DLS1
ON/OFF
DLS2
ON/OFF
FKA1
ON/OFF
FKA2
ON/OFF
FKA3
ON/OFF
HPSA
OPEN/CLSE
FKB1
ON/OFF
FKB2
ON/OFF
FKB3
ON/OFF
HPSB
OPEN/CLSE
DMND
XX.X mA
RSET
XX.X mA
CL.MA
XX.X mA

Outputs Mode and Sub-Mode Directory

ITEM
DISPLAY
FAN1
ON/OFF
FAN2
ON/OFF
FAN3
ON/OFF
FAN4
ON/OFF
FAN5
ON/OFF
MLV.R
ON/OFF
V.HPA
XXX.X %
V.HPB
XXX.X %
CC.A1
ON/OFF
DPE.R
XXX
CC.A2
ON/OFF
CC.A3
ON/OFF
LSV.A
ON/OFF
L.V.A2
ON/OFF
CC.B1
ON/OFF
CC.B2
ON/OFF
CC.B3
ON/OFF
LSV.B
ON/OFF
L.V.B2
ON/OFF
181
ITEM DESCRIPTION
GENERAL INPUTS
Start/Stop Switch
Indoor Fan Status-CIRA
Y1 Thermostat Input
Y2 Thermostat Input
Indoor Fan Status-CIRB
Y3 Thermostat Input
Y4 Thermostat Input
Demand Limit Switch 1
Demand Limit Switch 2
CIRCUIT INPUTS
Compressor A1 Feedback
Compressor A2 Feedback
Compressor A3 Feedback
High Pressure Switch A
Compressor B1 Feedback
Compressor B2 Feedback
Compressor B3 Feedback
High Pressure Switch B
4-20 MA INPUTS
4-20 ma Demand Signal
4-20 ma Reset Signal
Cap Req/Setpoint Signal
ITEM DESCRIPTION
GENERAL OUTPUTS
Fan 1 Relay
Fan 2 Relay
Fan 3 Relay
Fan 4 Relay
Fan 5 Relay
Minimum Load Valve Relay
Var Head Press Out Cir A
Var Head Press Out Cir B
OUTPUTS CIRCUIT A
Compressor A1 Relay
Comp A1 Load Percent
Compressor A2 Relay
Compressor A3 Relay
Liquid Line Solenoid A
Liquid Line Solenoid A2
OUTPUTS CIRCUIT B
Compressor B1 Relay
Compressor B2 Relay
Compressor B3 Relay
Liquid Line Solenoid B
Liquid Line Solenoid B2
COMMENT
COMMENT