Carrier 38APS025 Manual page 199

Gemini select, commercial air-cooled condensing units with comfortlink version 6.x controls 50/60 hz
Table of Contents

Advertisement

LEARNFNS
DESCRIPTION
SCT Delta for Comp A1
SCT Delta for Comp A2
SCT Delta for Comp B1
SCT Delta for Comp B2
LOADFACT (Capacity Control)
DESCRIPTION
Load/Unload Factor
Control Point
Return Air Temperature
Supply Air Temperature
Ramp Load Limited
Slow Change Override
Low Temperature Cooling
High Temperature Cooling
Minimum Comp. On Time
PM-COIL (Condenser Coil Preventative Maintenance)
DESCRIPTION
Coil Cleaning Srvc Inter
Coil Service Countdown
Coil Cleaning Maint.Done
Coil Cleaning Maint.Date
Coil Cleaning Maint.Date
Coil Cleaning Maint.Date
Coil Cleaning Maint.Date
Coil Cleaning Maint.Date
APPENDIX B — CCN TABLES (cont)
Maintenance Tables (cont)
VALUE
NNN.N
NNN.N
NNN.N
NNN.N
VALUE
CAPACITY CONTROL
NNN
NNN.n
NNN.n
NNN.n
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
VALUE
NNNNN
Range: 0 to 65,500
Default: 8760
NNNNN
NO/YES
00/00/00 00:00
00/00/00 00:00
00/00/00 00:00
00/00/00 00:00
00/00/00 00:00
199
UNITS
POINT NAME
F ( C)
A1SCTDT
F ( C)
A2SCTDT
F ( C)
B1SCTDT
F ( C)
B2SCTDT
UNITS
POINT NAME
SMZ
°F (°C)
CTRL_PNT
°F (°C)
RETURN_T
°F (°C)
SUPPLY_T
MODE_5
MODE_9
MODE_17
MODE_18
MODE_23
UNITS
POINT NAME
hours
SI_COIL
hours
CL_CDOWN
CL_MAINT
COIL_PM0
COIL_PM1
COIL_PM2
COIL_PM3
COIL_PM4
NETWORK
ACCESS
Read Only
Read Only
Read Only
Read Only
NETWORK
ACCESS
Read Only
Read/Write
Read/Write
Read/Write
Read Only
Read Only
Read Only
Read Only
Read Only
NETWORK
ACCESS
Read/Write
Read Only
Read Write
Read Only
Read Only
Read Only
Read Only
Read Only
515

Hide quick links:

Advertisement

Table of Contents
loading