Preventing Power Loss; Power Connection Guidelines - Cisco ASR 907 Hardware Installation Manual

Hide thumbs Also See for ASR 907:
Table of Contents

Advertisement

Preventing Power Loss

Products that have an AC power connection are required to have an external surge protective device (SPD)
Note
provided as part of the building installation to comply with the Telcordia GR-1089 NEBS standard for
electromagnetic compatibility and safety.
Do not use interface module and power supply ejector handles to lift the chassis; using the handles to lift
Caution
the chassis can deform or damage the handles.
Preventing Power Loss
Use the following guidelines to prevent power loss to the router.
• To prevent loss of input power, ensure that the total maximum load on each circuit supplying the power
• In some systems, you can use an UPS to protect against power failures at your site. Avoid UPS types
Use the information in the DC Power Supply Specifications table to estimate the power requirements and heat
dissipation of a Cisco ASR 907 Router based on a given configuration of the router. Determining power
requirements is useful for planning the power distribution system needed to support the router.

Power Connection Guidelines

This section provides guidelines for connecting the Cisco ASR 907 Router power supplies to the site power
source.
Never defeat the ground conductor or operate the equipment in the absence of a suitably installed ground
Warning
conductor. Contact the appropriate electrical inspection authority or an electrician if you are uncertain
that suitable grounding is available. Statement 213
The plug-socket combination must be accessible at all times because it serves as the main disconnecting
Warning
device. Statement 1019
The above statement is applicable only to the AC power supplies.
Note
Warning
This product requires short-circuit (overcurrent) protection, to be provided as part of the building installation.
Install only in accordance with national and local wiring regulations. Statement 1045
Cisco ASR 907 Router Hardware Installation Guide
76
supplies is within the current ratings of the wiring and breakers.
that use ferroresonant technology. These UPS types can become unstable with systems like the Cisco
ASR 907 Router, which can have substantial current draw fluctuations due to bursty data traffic patterns.
Installing the Cisco ASR 907 Router

Advertisement

Table of Contents
loading

Table of Contents