Indoor Fan Motor Control - Toshiba ras-m16g3dv-e Service Manual

Up to 4.5kw cooling capasity
Hide thumbs Also See for ras-m16g3dv-e:
Table of Contents

Advertisement

Item
1) Operation with (HH), (H+), (H), (L+), (L) or [AUTO] mode is carried
2. Indoor fan
motor
out by the command from the remote controller.
control
2) When the air speed mode [AUTO] is selected, the air speed varies
by the difference between Ta and Ts.
<COOL>
• Controlling operation in case when thermo of remote controller works
is same as a case when thermo of the body works.
• If the air speed has been changed once, it is not changed for
3 minutes. However when the air volume is exchanged, the air speed
changes.
• When cooling operation has started, select a downward slope for the
air speed, that is, the high position.
• If the temperature is just on the difference boundary, the air speed
does not change.
• Mode in the parentheses indicates one in automatic cooling
operation.
<HEAT>
Value in the parentheses indicates one when thermostat of the remote
controller works.
Value without parentheses indicates one when thermostat of the body
works.
• If the air speed has been changed once, it is not changed for 1
minute. However when the air speed is exchanged, the air speed
changes.
• When heating operation has started, select an upward slope for the
air speed, that is, the high position.
• If the temperature is just on the difference boundary, the air speed
does not change.
• Mode in the parentheses indicates one in automatic heating
operation.
• In Tc ≥ 60°C, the air speed increases by 1 step.
Operation flow and applicable data, etc.
Ta (˚C)
+3.0
HH
+2.5
(HH)
+2.0
H+ (HH)
+1.5
H (HH)
+1.0
L+ (H+)
+0.5
L (H)
Tsc
L (H)
–0.5
L (L+)
Ta (˚C)
L (L+)
(–0.5) –1.0
L+ (H)
Tsh
H (H+)
(+0.5) +1.0
H+
(HH)
(+1.0) +2.0
HH
(+1.5) +3.0
(HH)
(+2.0) +4.0
A
B
C
D
E
F
G
E
D
C
B
A
– 25 –
Description
HH > H+ > H > L+ > L > UL
Tc: Indoor heat
exchanger sensor
temperature