Frequency Fixed Operation (Test Run) - Toshiba ras-m16g3dv-e Service Manual

Up to 4.5kw cooling capasity
Hide thumbs Also See for ras-m16g3dv-e:
Table of Contents

Advertisement

Item
11. Frequency
<In case of wired remote controller>
fixed
Refer to 14-1.Test run setup.
operation
(Test run)
<In case of wireless remote controller>
1) When TEMPORARY button is pushed for 10 seconds
or more, "Pi!" sound is heard and the operation
changes to test run.
After approx. 3 minutes, a cooling operation starts
forcedly.
Check cool air starts blowing. If the operation does not
start, check wiring again.
2) To stop a test run, push TEMPORARY button once
again (Approx. 1 second).
Check wiring / piping of the indoor and outdoor units in
test run.
• In the TEST RUN, all LEDs together keep blinking.
• In order to prevent a serial operation, the TEST RUN
mode is released after 60 minutes have passed and
returns to the usual oeration.
Operation flow and applicable data, etc.
TEMPORARY button
Command frequency is approximately [S7]