Hobart 90 C 20 Operation And Maintenance Manual page 61

Engine-driven generator set
Table of Contents

Advertisement

C. Checking Operation of the Low Fuel Shutdown Assembly
The low fuel shutdown sensor (S54) has a TEST terminal, which permits testing of the sensor by elec-
trically simulating a low fuel condition. To check operation of the low fuel shutdown sensor:
(1) Turn on the generator set and operate it at idle speed.
(2) Using a jumper wire with an alligator clip on each end, ground the TEST terminal on the low fuel
shutdown sensor. The generator set engine should shut off immediately.
October 1/95 Revised
Location of Low Fuel Level Switch
Figure 7
OM-2031