Hobart 90 C 20 Operation And Maintenance Manual page 60

Engine-driven generator set
Table of Contents

Advertisement

OM-2031
7. Low Fuel Shutdown Assembly
A. Description
The low fuel shutdown assembly, when requested as an option by a customer, may be used with all
generator set specifications covered by this manual. It is identified by Hobart Part Number 285953 .
Its purpose is to stop the engine when the fuel level in the fuel tank becomes low before the unit runs
out of fuel. A liquid-level detector, mounted in the fuel tank, opens the power to the engine fuel valve
solenoid when fuel drops to a predetermined level in the fuel tank.
NOTE: Fuel tank MUST be refilled after a low-fuel shutdown before engine can be restarted.
B. Location of Relay and Low Fuel Sensor
Figure 6 shows where the low fuel relay is installed on the rear of the generator control box., and Fig-
ure 7 shows where the low fuel sensor is installed on the fuel tank. Engine schematic diagram
281886 in Chapter 6 identifies the low fuel shutdown sensor as item S54, and the low fuel relay as
K65.
1-3
Page 10
1. Control box
2. Relay retainer spring
3. Relay
4. Relay socket
5. Relay mounting bracket
Location for Relay on
Generator Control Box
Figure 6
October 1/95 Revised