Length overall
Width
Height overall
Weight
Length overall
Width
Height overall
Weight
Output power rating
Output Voltage
Rated load capacity
Frequency (cycles per second)
Output kilowatts
Power factor
Duty cycle
Operating speed at 400-Hz
Overload Capacity
(125 % of rated lad capacity
Overvoltage relay
Undervoltage relay
Overfrequency relay
Underfrequency relay
Overload relay
Undervoltage time delay relay trips
1-1
Page 4
PHYSICAL
BASIC UNIT
TRAILER-MOUNTED UNIT
GENERATOR
GENERATOR PROTECTIVE SYSTEM
Specifications and Capabilities
Figure 2 (Sheet 1 of 2)
82 inches (2082.8 mm)
36 inches (914.4 mm)
43 inches (1092.2 mm)
3050 pounds (1383.2 kg)
100 inches (2540 mm)
78 inches (1981.2 mm)
72 inches (1828.8 mm)
4950 pounds (2244.9 kg)
90 kVA
115/200-V
260-A
400-Hz
72-kW
0.8 PF
100%
2000 RPM
325 A
trips 130-V to 134-V; resets 125-V
trips 102-V or below; resets 110-V
trips 415-Hz to 425-Hz; resets 410-Hz
trips 375-Hz to 385-Hz; resets 385-Hz
trips at 112-kVA in less than 5 minutes
4 to 12 seconds