Approximate generator set weights are shown in
Figure 1-1. Use lifting bars inserted through the holes in
the skid to lift the unit. See the dimension drawings in
Section 2 for lifting hole locations.

1.3 Generator Set Inspection

Complete a thorough inspection of the generator set.
Check for the following:
1. Inspect the generator set for loose or damaged
parts or wires. Repair or tighten any loose parts
before installation.
2. Check the engine oil. Fill, if necessary, with the
recommended viscosity and grade of oil. Use
synthetic oil, API (American Petroleum Institute)
Service Class SG or higher.
Operation Manual, for additional information.

1.4 Location and Mounting

Install the generator set outdoors near the incoming gas
service. The generator set location must allow easy
access
for
maintenance
recommended distance from a structure is dependent
on state and local codes. See the dimension drawing in
Section 2 for the recommended clearance from
structures and non-combustible materials.
Locate the generator set so that the hot exhaust does
not blow on plants or other combustible materials. No
plants, shrubs, or other combustible materials are
allowed within 1.2 m (4 ft.) of the exhaust end of the
generator set.
Do not install the generator set where exhaust gas could
accumulate and seep inside or be drawn into a
potentially occupied building. Furnace and other similar
intakes must be at least 3 m (10 ft.) from the exhaust
end of the generator set.
12
Section 1 Installation
See TP-6804,
and
service.
The
Notice
DO NOT locate the generator set near patios,
decks, play areas, or animal shelters. Keep items
such as lawn furniture, toys, sports equipment,
and all combustible materials away from the
generator set exhaust outlet.
Remind family members, children, and visitors to
use caution near the generator set. Generator
sets connected to automatic transfer switches
start automatically during exercise periods and
power outages. Some generator set components
become hot when the generator set is running and
remain hot for a time after the generator set shuts
down.
1.4.1

Mounting Area

The generator set is shipped on an engineered
composite mounting pad. Prepare a flat, level mounting
area covered with a weed barrier and gravel or a
concrete mounting pad. Set the composite mounting
pad directly on the gravel or concrete.
Do not install the composite mounting pad directly on
grass, wood, or other combustible materials. Clear all
combustible materials, including plants and shrubs,
building materials, and lawn furniture, from an area at
least 1.2 m (4 ft.) beyond the exhaust end of the
generator set. See the dimension drawing in Section 2.
1.4.2

Concrete Mounting Pads

Kohler Co. offers optional concrete mounting pads that
are custom-designed for Model 14RESA/RESAL and
20RESA/RESAL generator sets.
four-inch thick pads are available. Four-inch pads are
recommended for storm-prone areas. See TT-1619 for
instructions to install the mounting pad, if necessary.
1.4.3

Exhaust Requirements

WARNING
Hot engine and exhaust system.
Can cause severe injury or death.
Do not work on the generator set until
it cools.
Three-inch and
TP-6803 1/15