located near the fuel solenoid valve.
Figure 1-11.
10. Connect and turn on the new fuel supply.
11. Reconnect the generator set engine starting
battery leads, negative (--) lead last.
12. Reconnect the utility power to the generator.
13. Start the generator set by pressing the RUN button
on the generator set controller.
14. Check for leaks using a gas leak detector.
1
2
1. Orifice fitting (see detail)
2. Hose barb fitting
Figure 1-12 14RESA/RESAL Fuel System Showing Orifice Fittings (generators built after June 26, 2014)
TP-6803 1/15
See
15. Run the generator set and check the operation.
16. Press the OFF button to shut down the generator
set.
Conversion from LPG to Natural Gas
To convert from LPG to natural gas, repeat the steps
above, removing the LPG fuel orifice and installing the
NG fitting. Connect DSAI leads 65 and N3 together for
natural gas.