Manual Reset Hard Lockouts - Prestige Solo 110 Installation And Maintenance Manual

Table of Contents

Advertisement

9.0
ACVMax Operation
Code
Lockout Message
E1
Failed Ignition
E2
False Flame
E3
High Boiler Temperature
E5
Blower Speed
E8
Flame Circuit Error
E9
Gas Valve Circuit Error
E13
Reset Limit Reached
E15
Sensor Drift
E16
Supply Sensor Stuck
E17
Return Sensor Stuck
E18
Sensor Failure
E21
Internal Control Fault
E30
Supply Sensor Shorted
E31
Supply Sensor Open
E43
Return Sensor Shorted
E44
Return Sensor Open
E47
Water Pressure Sensor Error Water pressure sensor is disconnected or broken.
E80
Return > Supply
E87
External Limit Open

Manual Reset Hard Lockouts

The burner failed to light after 5 ignition attempts.
A flame is being detected prior to ignition.
Boiler temperature has reached 210°F [99ºC]
Blower is not at correct speed or speed signal is not being received
by control module.
Flame circuit test failed.
Gas valve circuit test failed.
Resets are limited to 5 every 15 minutes.
Supply or return sensor reading has drifted.
Supply sensor reading is not changing.
Return sensor reading is not changing.
Supply or return sensor reading changed very rapidly.
A / D conversion error.
A short circuit has been detected in the boiler supply temperature
sensor circuit.
An open circuit has been detected in the boiler supply temperature
sensor circuit.
A short circuit has been detected in the boiler return temperature
sensor circuit.
An open circuit has been detected in the boiler return temperature
sensor circuit.
Return temperature is higher than supply temperature.
An external manual reset limit has opened