9.0
ACVMax Operation

9.7.4 Select CH1 Reset Curve

Select CH1 Reset Curve prompts the installer to select an outdoor reset curve
for a CH1 heating call when an Outdoor Reset option is chosen in Select CH
Demand. Outdoor reset curve presets are available to cover most applica-
tions. The outdoor reset curve can also be adjusted to any desired settings in
the Installer Menu. Press the UP or DOWN buttons to select the outdoor
reset curve appropriate for the type of heating system then press the OK but-
ton to store the setting.

9.7.5 Select CH2 Reset Curve

Select CH2 Reset Curve prompts the installer to select an outdoor reset curve
for a CH2 heating call when an Outdoor Reset option is chosen in Select CH
Demand. Outdoor reset curve presets are available to cover most applica-
tions. The outdoor reset curve can also be adjusted to any desired settings in
the Installer Menu. Press the UP or DOWN buttons to select the outdoor
reset curve appropriate for the type of heating system then press the OK but-
ton to store the setting.
Preset
Low Mass Radiant
High Mass Radiant
Cast Iron Baseboard
Finned Tube Baseboard
Radiators
Fan Coil

9.7.6 Set Warm Weather Shutdown Temperature

Warm Weather Shutdown prompts the installer to enter an optional outdoor
temperature at which to disable the central heating function and any circu-
lators placed into constant circulation with the Pump Constant Circulation
setting. The Prestige will continue to respond to a domestic hot water call
or a 0-10V Modulation Signal when the outdoor temperature exceeds the
Warm Weather Shutdown Temperature setting.
RIGHT buttons to adjust the Warm Weather Shutdown Temperature then
press the OK button to store the setting. The Warm Weather Shutdown
icon
is displayed on the home screen when the outdoor temperature
reaches the Warm Weather Shutdown Temperature.

9.7.7 CH EZ Setup Complete

EZ Setup Complete informs the installer upon completion of all necessary
steps that the EZ setup is complete. Press the OK button to return to the
EZ Setup Menu.
Default: Finned Tube Baseboard
Default: Low Mass Radiant
Table 3: Outdoor Reset Preset Selections
Minimum Setpoint
80ºF [27ºC]
80ºF [27ºC]
100ºF [38ºC]
120ºF [49ºC]
120ºF [49ºC]
140ºF [60ºC]
Default: OFF
Press the LEFT or
47
Select CH1 Outd. Curve
180ºF
120ºF
64ºF
0ºF
Current Settings
Maximum Setpoint
140ºF [60ºC]
120ºF [49ºC]
170ºF [77ºC]
180ºF [82ºC]
170ºF [77ºC]
180ºF [82ºC]
Warm Weather Shutdown
O
O
EZ Setup Complete
Heating EZ setup is complete.
Additional changes can be made in
the Installer Menu if required.
Press OK to return to EZ Setup Menu
78ºF