11.0
Start-Up Procedures
e. Press the LEFT and RIGHT buttons to
adjust the firing rate from 1% to 100%.
Hold down the LEFT or RIGHT but-
ton to rapidly increase or decrease the
firing rate.
Table 4: Recommended Combustion Levels
Natural Gas
All Models
O2 Min.
2.30%
O2 Max.
5.30%
CO2 Min.
8.80%
CO2 Max.
10.50%
CO Max.
100 ppm
f. Press the OK button while the FAN icon
is highlighted to shutdown the burner.
g. Cycle power to the Prestige once com-
bustion testing is complete to return to
normal operation.
WARNING
The combustion levels should be mea-
sured at high firing rate. If the combus-
tion levels are not within the range given
in Table 4 for the firing rate, shut the
boiler down and contact ACV-Triangle
Tube Technical Support. Failure to com-
ply with this requirement could result in
severe personal injury, death or substan-
tial property damage.
If the combustion levels during HIGH
FIRE (100%) is outside the recommended
combustion settings adjust the THROT-
TLE SCREW (see Figs. 16, 17, & 18 on
page 29) according to Table 5.
3. Once the combustion level is set at high fire
(100%), manually place the boiler into low
fire (1%) mode by pressing the LEFT but-
ton to adjust firing rate down.
Propane
Propane
Solo 80/110/
Solo 299/399
155/175/250
2.70%
3.70%
4.70%
5.20%
10.70%
10.00%
12.00%
11.00%
100 ppm
100 ppm
4. If the CO2 combustion level during low
fire (1%) is not within +/- 0.2 of the com-
bustion level measured at high fire, adjust
the plastic OFFSET SCREW under the
cover screw on the top of the gas valve (see
Figs. 16, 17, & 18 on page 29) according to
Table 6.
Direction
Clockwise
Decrease CO 2
Counter-Clockwise
Table 5: Throttle Screw - High Fire
Direction
Clockwise
Counter-Clockwise
Table 6: Offset Screw - Low Fire
Measure Input - Natural Gas Only
c
1. Ensure the boiler is firing at maximum firing
rate. To manually place the boiler into high
fire mode, reference page 60.
2. Operate the unit for approximately 10
minutes.
3. Turn off all gas appliances within the build-
ing, except the PRESTIGE Solo.
4. At the gas meter, record the time required
to use one cubic foot of gas.
5. Calculate Natural gas input using the fol-
lowing equation:
3600 x 1000 / number of second recorded
for one cubic foot of gas = BTU/H.
6. The BTU/H calculated should approximate
the input rating listed on the unit.
61
155/175/250
80/110
299/399
Increase CO 2
Decrease CO 2
Decrease O 2
Increase O 2
Increase CO 2
Increase O 2
Decrease O 2
All Units
Increase CO 2
Decrease O 2
Decrease CO 2
Increase O 2