Clean Condensate Drain Assembly; Check Ventilation Air Openings; Inspect Vent And Combustion Air Piping; Check Boiler System - Prestige Solo 110 Installation And Maintenance Manual

Table of Contents

Advertisement

17.0 Maintenance Procedures
17.6 Clean
Condensate
Assembly
Loosen the retaining nut from the condensate
drain assembly and disconnect the assembly
from the boiler.
Empty any water from the trap and drain
assembly. Flush with fresh water as necessary
to clean.
Check the drain piping from the condensate
drain assembly to the drain. Flush to clean as
necessary.
Reassemble the condensate drain assembly
onto the boiler by tightening the retaining nut
with rubber seal onto the boiler. Hand tight
only.
Remove the fill plug on the condensate drain
assembly and fill with water. See Fig. 14 on
page 25.
Replace the fill plug on drain assembly.

17.7 Check Ventilation Air Openings

Verify that all ventilation openings to the
mechanical room or building are open and
unobstructed. Check the operation and wiring
of any automatic ventilation dampers.
Check and verify the vent discharge and the
combustion air intake are free of debris and
obstructions.
17.8 Inspect Vent and Combustion Air
Piping
Visually inspect the venting system and com-
bustion air piping for blockage, deterioration
of gaskets or leakage. Repair any deficiencies.
Verify that the combustion air inlet piping is
connected, sealed and properly supported.
Drain
WARNING
Failure to inspect the vent system and
combustion air inlet piping and to have
any conditions repaired, can result in
severe personal injury or death.

17.9 Check Boiler System

Verify all system components are correctly
installed and operating properly.
Check the cold fill pressure for the system, typ-
ical cold water fill pressure is 12 psig.
Verify the system pressure, as the unit operates at
high temperature, to ensure the pressure does not
exceed 25 psig. Excessive pressure reading indi-
cates expansion tank sizing is incorrect or system
performance problems.
Inspect air vent and air separators in the sys-
tem. Remove the caps on automatic air vents
and briefly depress the valve stem to flush
vent. Replace the cap when completed. Ensure
vents do not leak, replace any leaking vents.
Verify boiler fluid pH level is between 6.0 and
8.0.
Check and verify inhibitor /antifreeze concen-
tration within the boiler water meets
inhibitor/antifreeze manufacturer's specifica-
tions.
If necessary contact a boiler water treatment
company for a chemical analysis.