Engineering via SICAM TOOLBOX II
4.1.9.3

Test Functions

For the examination of the parameterized automation units and their data flows, the following
test functions are available:
·
Data flow test
·
Message simulation
·
Topology test
State of
spontaneous
data points
simulation of
spontaneous
data points
check con-
nection to AUs

4.1.9.3.1 Status Of Spontaneous Data Points

With the tool "Data Flow Test" data streams (flow of messages) can be simultaneously logged
and visualized. For a subsequent analysis - also at another location - a recording can take
place with the Interface Recorder.
The function Simultaneous log serves for the recording of messages within the internal da-
ta flow of an automation unit. In protocol elements, the data flow from and to other automation
units can also be acquired.
The following data can (with change of the spontaneous data) be simultaneously logged:
·
Change of state of inputs/outputs
·
Communication from and to protocol elements
·
Data traffic from and to the application program
·
Data traffic from and to special functions (for example set counters, set time)
By means of triggering a General Interrogation all spontaneous input signals can be simulta-
neously logged at any arbitrary time.
You find the instruction for this test function in the SICAM TOOLBOX II Online Help, chapter
"Service Programs", section "Data Flow Test".
You find further information in the manual SICAM RTUs Common Functions System and
Basic System Elements, chapter "System Services", section "Data Flow Test".
196
selection AU
data flow
test
selection AU
message
simulation
total network or
selection AU
topology
test
define TOOLBOX
filters
start record
select test points
select message
display format
play record
select message
send message(s)
display format
logging of the
connected AUs
SICAM RTUs, SICAM AK 3 User Manual