Parameter Comparison - Siemens SICAM RTU User Manual

Table of Contents

Advertisement

All settings that have been performed in the SICAM TOOLBOX II are thereby saved jointly on
the SD card of the target system:
·
Configuration parameters
·
System-technical parameters
·
Process-technical parameters (if they have been transformed previously)
·
Application program (if code has been generated previously)
After the loading of the parameters an automatic startup of the target system is performed. For
each selected automation unit a corresponding notification appears subsequently.
For the loading of the parameters there are different variants available:
·
Load intelligent
─ only the changed parameters are loaded into the target system
─ can be applied locally or remotely
·
Load unconditional
─ all parameters are loaded into the target system
─ can be applied locally or remotely
·
Initialize
─ all parameters are deleted in the target system, and all parameters newly transferred
─ can be applied only with the locally connected automation unit
─ is used for the first loading of an automation unit or of a basic system element
You find the details thereto in the SICAM TOOLBOX II Online Help, chapter "Service Pro-
grams", section "Parameter Loader".
Caution
During a loading operation, a power down off of the master control element is to be absolutely avoided,
since the data on the flash card could be destroyed as a result.
4.1.9.2

Parameter Comparison

With tool "Parameter Loader" you can check whether the parameter status in the destination
system is current. You can select an automation unit and start the comparison via the menu
Parameter | Comparison Aus <-> Toolbox .
For each selected automation unit appears the indication whether the parameters are current
or not current.
SICAM RTUs, SICAM AK 3 User Manual
DC2-028-2.03, Edition 07.2016
Engineering via SICAM TOOLBOX II