Step 8 - Mount Electric Heater (Optional) - Carrier 40MBAB Installation Instructions Manual

Air handler unit ductless system
Hide thumbs Also See for 40MBAB:
Table of Contents

Advertisement

40MBAB: Installation Instructions
Triple Evacuation Method
The triple evacuation method should be used when vacuum pump is not
capable of pumping down to 500 microns and system does not contain
any liquid water. Refer to Fig. 42 and proceed as follows:
1. Attach refrigeration gauges and evacuate system down to 28 in. of
mercury and allow pump to continue operating for an additional 15
minutes.
2. Close service valves and shut off vacuum pump.
3. Connect a nitrogen cylinder and regulator to system and flow
nitrogen until system pressure is 2 psig.
4. Close service valve and allow system to stand for 1 hour. During this
time, dry nitrogen can diffuse throughout the system absorbing
moisture.
5. Repeat this procedure as indicated in Fig. 42. The system should
now be free of any contaminants and water vapor.
BREAK VACUUM WITH DRY NITROGEN
BREAK VACUUM WITH DRY NITROGEN
CHECK FOR TIGHT, DRY SYSTEM
(IF IT HOLDS DEEP VACUUM)
RELEASE CHARGE INTO SYSTEM
Fig. 42 —Triple Evacuation Method
Final Tubing Check
Check to be certain factory tubing on both the indoor and outdoor unit has
not shifted during shipment. Ensure tubes are not rubbing against each
other or any sheet metal. Pay close attention to the feeder tubes, making
sure wire ties on feeder tubes are secure and tight.

Step 8 - Mount Electric Heater (Optional)

Heater Kits
This unit is not equipped with an electric heater package. A factory-approved,
field-installed, ETL listed heater package is available from your equipment
supplier. Factory-authorized, field-installed electric heater packages are available
in sizes 5kW through 25kW. Electric heaters that are not factory approved may
cause damage which would not be covered under the equipment warranty. Review
the product data literature for all available accessory kits.
Table 8 — Accessories
Name
Owner's and Installation Manual
Seal
Screw
Electric Auxiliary Heating
Wiring Diagram
Circuit Breaker Label
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
EVACUATE
WAIT
EVACUATE
WAIT
EVACUATE
Shape
Quantity
NOTE: Installation must be performed by an authorized dealer or
specialist. Use recommended PPE when installing the unit.
Specification of electric auxiliary heat modules: 5kW, 8kW, 10kW, 15kW,
20kW, 25kW.
Table 9 — Auxiliary Heater Compatibility
MODEL (Btu/h)
18K
24K
30K
36K
48K
60K
Table 10 — Power Requirements for Heaters
Heater
Model
Kit Size
Number
(KW)
EHKMB0
5
5KN
EHKMB0
8
8KN
EHKMB1
10
0KN
EHKMB1
15
5KN
EHKMB2
20
0KN
EHKMB2
25
5KN
NOTE: The EHKMA series of heaters is NOT compatible with the
40MBAB air handler.
A220818
This electric auxiliary heat module is internally mounted in the air
handler. DO NOT mount in the ductwork.
If the unit needs to be equipped with the electric auxiliary heat module, check
the electric auxiliary heat module specification that is compatible with the
unit to avoid unnecessary consequences caused by improper matching and
refer to Product Data Manual.
INSTALLATION REQUIREMENTS
NOTE: Installation of Auxiliary Electric Heat Module should be
completed before installing the discharge ductwork to
insure proper alignment of the inside support brackets.
Before installation, check the list of electric auxiliary heat modules and
physical objects. After transportation, check whether the electric heat
module is damaged. If any damage is detected, contact the after-sales
personnel immediately.
1
NOTE: A separate power source is required for an Auxiliary Electric
Heater. These units do NOT support a SINGLE POINT
electrical connection when utilizing auxiliary heat.
1
7
1
1
15
5kW
8kW
10kW
15kW
Y
Y
Y
-
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
-
Y
Y
Y
-
-
Y
Y
MCA
MCA
MCA
Circuit
Circuit
Circuit
1 208V/
2 208V/
3 208V/
230V
230V
230V
23.0/
27.0
37.0/
42.0
46.0/
53.0
23.0/
46.0/
27.0
53.0
46.0/
46.0/
53.0
53.0
23.0/
46.0/
46.0/
27.0
53.0
53.0
CAUTION
20kW
25kW
-
-
-
-
-
-
Y
-
Y
-
Y
Y
MOPD
MOPD
Circuit
Circuit
1 208V/
2 208V/
230V
230V
25.0/
30.0
40.0/
45.0
50.0/
60.0
25.0/
50.0/
30.0
60.0
50.0/
50.0/
60.0
60.0
25.0/
50.0/
30.0
60.0