Chapter 2
Installing the Device
Figure 4: Panel Mounting
1. Screw
2. Panel/DIN Rail Adaptor
2.
Install the supplied screws to secure the adapters to the panel.
Section 2.2

Connecting Power

The RS400 supports a single integrated high AC/DC or low DC power supply
NOTE
• For 88-300 VDC rated equipment, an appropriately rated circuit breaker must be installed.
• For 100-240 VAC rated equipment, an appropriately rated circuit breaker must be installed.
• Use only #16 gage copper wiring when connecting terminal blocks.
• A circuit breaker is not required for 12, 24 or 48 VDC rated equipment.
• Power input terminals have reverse polarity protection for 12, 24 and 48 VDC rated equipment.
• Equipment must be installed according to applicable local wiring codes and standards.
The following sections describe how to connect power to the device:
Section 2.2.1, "Connecting AC Power"
Section 2.2.2, "Connecting DC Power"
8
1
1
RUGGEDCOM RS400
Installation Guide
2
Connecting Power