INSTALLER SET-UP MENU
SELECTING LOW BALANCE POINT OPTION
Menu 16 allows you to select a low balance point setting when the thermostat is
configured for Heat Pump or Fossil Fuel and an outdoor sensor is used. When
the outdoor temperature falls below the balance point setting, the compressor is
locked out and only auxiliary electric heat or fossil fuel furnace is used for
heating. The factory default is OFF. Touch the UP or DOWN arrows to select a
low balance point setting.
Next
Back
Adjustable from OFF, -17° to 25°C
Remote outdoor sensor must be used
37