The following values are displayed in the operating display of the SIMOTRAS 6SG70.
st
1
line
nd
2
line
rd
3
line
th
4
line
Control bits from OP1S operator panel:
(see also function diagram "OP1S operating display" (Section 8, Sheet Z123) and the OP1S
operating instructions)
Data are exchanged between the OP1S and SIMOTRAS 6SG70 converter via the G-SST1
interface (RS485) and USS protocol.
The OP1S operator panel transfers the following control bits in process data word 1 in the USS
message:
Key on OP1S
ON key / OFF key (I / 0)
Reset
Jog
Reverse
Increase key
Decrease key
*) These binectors (control bits) are available for all control tasks (when parameterized
accordingly), but are not normally used with SIMOTRAS 6SG70 converters.
7.3

Parameterization procedure

Parameterization is the process of changing setting values (parameters) via the operator panel,
activating converter functions or displaying measured values.
Parameters for the basic converter are called P, r, U or n parameters. Parameters for an optional
supplementary board are called H, d, L or c parameters.
The basic unit parameters are displayed first on the PMU, followed by the technology board
parameters (if such a board is installed). It is important not to confuse the parameters of the S00
technology software of the basic unit with the parameters of an optional supplementary board (e.g.
T300).
Depending on how parameter P052 is set, only some parameter numbers (see Section 11,
Parameter List) are displayed.
7.3.1

Parameter types

Display parameters are used to display current quantities such as the main setpoint,
setpoint/actual value difference of speed controller, etc. The values of display parameters are read-
only values and cannot be changed.
Setting parameters are used to both display and change quantities such as the rated motor
current, thermal motor time constant, speed controller P gain, etc.
Indexed parameters are used to both display and change several parameter values which are all
assigned to the same parameter number.
SIEMENS AG
6SG7000-0BA76
SIMOTRAS HD
Operating Instructions
Actual motor current value r019
#
Actual speed controller value r025
*
Speed setpoint r028
Operating state r059
ON / OFF1
Acknowledge
Inching
Enable positive direction of rotation
Enable negative direction of rotation
Increase motorized potentiometer
Decrease motorized potentiometer
0
Function
Bus addr.
Bit in PZD word1
Binector *)
(connector K2001)
Bit 0
Bit 7
Bit 8
Bit 11
Bit 12
Bit 13
Bit 14
Start-up
B2100
B2107
B2108
B2111
B2112
B2113
B2114
7-5