SIMOTRAS HD – QUICK START INSTRUCTIONS
(Copy of carton supplied with this operating manual)
Requirements:
Factory settings in place, connected according to suggested connection in Section 6.1
Access authorization
P051 = 40 all parameters can be modified
Motor data
P100
Rated motor current (in amps)
P114
Thermal time constant of motor (in minutes)
P490.001
Type of temperature sensor on terminal 22/23 (factory setting: 1)
0 .. no temperature sensor present
1 .. KTY84
4 .. PTC with Rn = 1330 Ohm: when R < Rn: B0184 = 0, when R > Rn: B0184 = 1
Speed sensing with analog tachometer (displayed on r002)
P083 = 1
Tachometer connected to terminals 103 and 104
P741
Tachometer voltage at maximum speed (approx. 8 V to +270.00) (factory setting: 60.00 V)
Speed sensing with pulse encoder (displayed on r024)
P083 = 2
Pulse encoder connected to terminals 28/29 and 30/31
P140 = 1
Pulse encoder has two pulse traces that are displaced by 90° (factory setting: 1)
P141
Number of pulses of pulse encoder (factory setting: 250 pulses per revolution)
P142 = 1
Pulse encoder outputs 15V signals (factory setting: 1)
P143
Maximum speed (rpm) (factory setting: 1450 rpm)
Speed setpoint normalization
P401
Speed setpoint that must be attained under control by master switch (factory setting: 60 %)
for lifting gear: approx. 60%, for travel gear: approx. 100%
U628
Threshold for zero delay angle setting
Current limits (actual current value displayed on r019)
P171
For torque direction I (as % of P100) (factory setting: +200 %)
P172
For torque direction II (as % of P100) (factory setting: -200 %)
Current controller
P155
Controller gain Kp (factory setting: 0.2)
P156
Reset time Tn (factory setting: 0.02 s)
Speed controller
P225
Controller gain Kp (factory setting: 3.0)
P226
Reset time Tn (factory setting: 0.2 s)
P200
Smoothing of actual speed value (factory setting: 10 ms)
Ramp-function generator
Ramp times for closed-loop operation
P303
Ramp-up time (factory setting: 10 s)
P304
Ramp-down time (factory setting: 10 s)
P305
Lower transition rounding (factory setting: 0 s) P309
P306
Upper transition rounding (factory setting: 0 s) P310
Start pulse for speed controller
U651
Start pulse for clockwise movement (= lifting) (as % of P100) (factory setting: 0 %)
U652
Start pulse reduction factor for anti-clockwise movement (= lowering) (factory setting: 50 %)
Rotor contactor stepping
U634
Speed at which the rotor contactor for stage 2 is switched in (factory setting: 50%)
U636
Speed at which the rotor contactor for stage 3 is switched in (factory setting: 75%)
U638
Speed at which the rotor contactor for stage 4 is switched in (factory setting: 90%)
U630
Speed at which the rotor contactor for stage 1 is prematurely switched in when in "Delay lowering" mode
(counter-torque operation) (factory setting: -1%)
Ramp-down monitoring
U441
When the travel command is cancelled, the motor must have reached its minimum speed (P370) within
the time specified here, otherwise the fault message F023 is activated (factory setting: 10.5 s)
(Recommended value: highest of P304 + 10% and P308 + 10%)
Setpoint reduction with pre-limit switch
U608
When approaching a pre-limit switch, the speed setpoint is multiplied by the value specified here
(factory setting: 15%)
SIEMENS AG
6SG7000-0BA76
SIMOTRAS HD
Operating Instructions
(Factory setting: 10 min)
(0 ... monitoring switched off)
P491
Alarm temperature (factory setting = 20°C)
Ramp times for open-loop operation
P307
Ramp-up time (factory setting: 10 s)
P308
Ramp-down time (factory setting: 10 s)
Lower transition rounding (factory setting: 0 s)
Upper transition rounding (factory setting: 0 s)
Start-up