01.04
7.6

Start-up procedure

WARNING
The converter is at a hazardous voltage level even when the line contactor is open. The gating
board (board mounted directly to lower part of housing) has many circuits at hazardous voltage
levels.
Non-observance of the safety instructions given in this manual can result in death, severe
personal injury or substantial property damage.
NOTE
The start-up procedure described below applies in situations where the SIMOTRAS HD converter is
connected to the system in accordance with the suggested connection plan. If this is not the case,
additional or other measures may be required in certain instances.
7.6.1

Access authorization

P051 . . . Key parameter
0 Parameter cannot be changed
40 Parameter can be changed
P052 . . . Selection of parameters to be displayed
0 Only parameters that are not set to default are visible
3 All parameters are visible
7.6.2

Adjustment of converter rated currents

The rated converter current must be adjusted by the setting in parameter P076.001 (in %) if:
rated
7.6.3

Adjustment to actual converter supply voltage

P078.001
Rated RMS value of actual voltage applied in SIMOTRAS HD (in Volts)
7.6.4

Input of motor data

The motor data as given on the motor rating plate must be entered in parameters P100 and P114.
P100
Rated motor current (in amps)
P114
Thermal time constant of motor (in minutes)
P490.001
Temperature sensor on terminals 22/23 for monitoring the motor temperature
0
1
2
3
4
5
1)
PTC thermistor according to DIN 44081 / 44082 with specified R at rated response
temperature. When a PTC thermistor is selected as the temperature sensor, it is not
necessary to set parameters P491 and P492 (alarm and trip temperatures). These two
temperatures are predetermined by the type of PTC thermistor installed. Whether an alarm or
fault is output when the operating point of the PTC thermistor is reached depends on how the
relevant input is parameterized (P493.F or P494.F).
P491
Alarm temperature (factory setting = 20°C)
SIEMENS AG
6SG7000-0BA76
SIMOTRAS HD
Operating Instructions
max
.
motor
current
<
converter
current
No temperature sensor
KTY84
PTC thermistor with R
PTC thermistor with R
PTC thermistor with R
PTC thermistor with R
0
5 ,
=600Ω 1)
n
=1200Ω 1)
n
=1330Ω 1)
n
=2660Ω 1)
n
Start-up
7-9