Preventive Maintenance

Water Coil Maintenance
1. Keep all air out of the water. An open loop system should be checked to ensure that the well head is not allowing air to infiltrate the
water line. Lines should always be airtight.
2. Keep the system under pressure at all times. It is recommended in open loop systems that the water control valve be placed in the
discharge line to prevent loss of pressure during off cycles. Closed loop systems must have positive static pressure.
NOTE: On open loop systems, if the installation is in an area with a known high mineral content (125 PPM or greater) in the water, it is
best to establish with the owner a periodic maintenance schedule so the coil can be checked regularly. Should periodic coil cleaning be
necessary, use standard coil cleaning procedures which are compatible with either the cupronickel or copper water lines. Generally, the
more water flowing through the unit the less chance for scaling.
Other Maintenance
Filters
Filters must be clean to obtain maximum performance. They should be inspected monthly under normal operating conditions and be
replaced when necessary. Units should never be operated without a filter.
Condensate Drain
In areas where airborne bacteria produce a slime in the drain pan, it may be necessary to treat chemically to minimize the problem. The
condensate drain can pick up lint and dirt, especially with dirty filters. Inspect twice a year to avoid the
possibility of overflow.
Blower Motors
Blower motors are equipped with sealed ball bearings and require no periodic oiling.
Hot Water Generator Coil
See Water Coil Maintenance section above.
Air Coil
The air coil must be cleaned to obtain maximum performance. Check once a year under normal operating conditions and, if dirty, brush or
vacuum (with a brush attachment) clean. Care must be taken not to damage the aluminum fins while cleaning.
CAUTION: Fin edges are sharp.

Replacement Procedures

Obtaining Parts
When ordering service or replacement parts, refer to the model number and serial number of the unit as stamped on the serial plate
attached to the unit. If replacement parts are required, mention the date of installation of the unit and the date of failure, along with an
explanation of the malfunctions and a description of the replacement parts required.
In-Warranty Material Return
Material may not be returned except by permission of authorized warranty personnel. Contact your local distributor for warranty return
authorization and assistance.
LX ULTRA SERIES INSTALLATION MANUAL