DESCRIPTION
These outdoor condensing units are completely assembled,
piped and wired at the factory to provide one-piece shipment
and rigging. Each unit is pressurized with a holding charge of
refrigerant-22 for storage and/or shipping.
The compact design, clean styling, and quiet operation make
these condensing units suitable for almost any outdoor
location. On rooftops . . . because they weigh much less than
a single package unit of similar capacity and are much easier
to rig and support. At ground level . . . because their ample
sub-cooling capacity allows them to be located 18 meters (60
feet) below the evaporator coil.
All sheet metal parts are constructed of commercial grade
(G90) galvanized steel. Before painting, each part is thoroughly
cleaned to remove any grease or dirt from its surfaces. The
external parts are then coated a "desert sand" powder paint to
assure a quality finish for many years. This coating system has
passed the 750 hour, salt spray test per ASTM Standard B117.
All models include a 1-year limited warranty on the complete
unit. The compressor carries an additional 4-year warranty.
A matching line of Evaporator Blower units is also offered to
meet your precise capacity and air handling requirements.
FEATURES
Condenser coil constructed of rifled copper tubes and
louvered aluminum fins for durability and long lasting
efficient operation.
Permanently attached base rails with fork lift slots and lifting
holes. This design allows for 3-way fork lift access and
overhead rigging.
Both high and low pressure controls.
SPLIT-SYSTEM
AIR-COOLED
CONDENSING UNITS
O
H3CE180 & 240
O
O
15 AND 20 NOMINAL TONS
Solid state motor protection to prevent the compressor from
operating at an unsafe condition.
Ball bearing condenser fan motors with 5/8 inch shafts.
Color-coded power and control wiring for easier service and
troubleshooting.
Anti-short cycle timer to protect the compressor.
A lockout circuit to prevent the unit from cycling on safety
control.
A 24-volt temperature control circuit.
Standard unit low ambient operation to (35°F).
A filter-drier
compartment for field installation near the evaporator coil).
Service valves with a back-seating access port for pressure
testing the system. Copper stub-outs are factory mounted
on the suction and liquid service valves to simplify the field
piping connections.
Separate panel for easy access to the control box without
affecting air flow across the condenser coil.
Exterior access to service pressure port connections.
Packaging suitable for outdoor storage.
An optional Phenolic coating is available where the
condenser coils are fully dipped in a phenolic coating
process to provide longer life in corrosive conditions.
550.23-TG3Y (398)
®
(shipped in the unit's compressor

Advertisement

loading

Summary of Contents for York H3CE180

  • Page 1 550.23-TG3Y (398) ® SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS H3CE180 & 240 15 AND 20 NOMINAL TONS DESCRIPTION • Solid state motor protection to prevent the compressor from These outdoor condensing units are completely assembled, operating at an unsafe condition. piped and wired at the factory to provide one-piece shipment •...
  • Page 2: Table Of Contents

    Holding charge is the amount in the unit as shipped from the factory. Operating refrigerant charge is for the condensing unit and the matching York air handler, but does not include the charge in the interconnecting piping. See the Refrigerant Line Charge Table to determine the additional refrigerant charge required for interconnecting piping.
  • Page 3: Unit Dimensions & Clearances

    550.23-TG3Y UNIT DIMENSIONS & CLEARANCES C O M P R E S S O R A N D F A N M O T O R A C C E S S E X T E R N A L P R E S S U R E F A N M O T O R A I R G A U G E F I T T I N G S...
  • Page 4 550.23-TG3Y SYSTEM GROSS COOLING CAPACITIES AND POWER REQUIREMENTS H3CE180 WITH K1EU180 85 °F Air Entering Condenser 95 °F Air Entering Condenser Air Ent. Power Air Temperature Entering Evaporator, Dry Bulb Power Air Temperature Entering Evaporator, Dry Bulb Evaporator Input Input...
  • Page 5 550.23-TG3Y SYSTEM GROSS COOLING CAPACITIES AND POWER REQUIREMENTS - Cont’d. H3CE240 WITH L3EU240 85 °F Air Entering Condenser 95 °F Air Entering Condenser Air Ent. Power Air Temperature Entering Evaporator, Dry Bulb Power Air Temperature Entering Evaporator, Dry Bulb Evaporator Input Input Total Sens Total Sens Total Sens Total Sens Total Sens Total Sens Total Sens Total Sens...
  • Page 6: Field Wiring

    550.23-TG3Y FIELD WIRING H 3 C E 1 8 0 / K 1 E U 1 8 0 3 - P H A S E 3 - P H A S E L I N E V O L T A G E L I N E V O L T A G E P O W E R S U P P L Y P O W E R S U P P L Y...
  • Page 7: Suction Line Data

    2 contactor 3M to energize. TLA opens as the circuit path is open if: temperature falls below 50 F and closes as the ambient rises above 60 F. TLA is used on the H3CE180, not the H3CE240. • the lock out relay contacts LOR-1 are open, OR •...
  • Page 8 550.23-TG3Y CAUTION: Repeatedly resetting the lock out may cause The low pressure bypass timer 1TR leaves the 1TR-1 contacts closed upon the start of a call for cooling until its 90 second damage to the unit. (nominal) timer has expired. This bypasses the low pressure switch during start up.
  • Page 9 550.23-TG3Y GUIDE SPECIFICATION - H*CE180 THROUGH 240 V. Refrigeration Components - Refrigeration system I. General shall contain the following: A. Units shall be manufactured in a facility registered under • the ISO 9002 manufacturing quality standard. High and low pressure cut-outs •...
  • Page 10 550.23-TG3Y GUIDE SPECIFICATION - H*CE180 THROUGH 240 (cont’d) B. Coil Guard D. Phenolic Coating on Condenser Coil Condenser coils shall be dipped in a four-coat phenolic Field installed decorative grille shall be placed on the coating process to provide longer life in corrosive condi- units to provide further coil protection.
  • Page 11 550.23-TG3Y Unitary Products Group...
  • Page 12 550.23-TG3Y P.O. Box 1592, York, Pennsylvania USA 17405-1592 Supersedes: 550.23-TG3Y (597) Subject to change without notice. Printed in U.S.A Copyright © by York International Corporation 1998. All Rights Reserved. Codes: EBY, EGY...

This manual is also suitable for:

H3ce240