Hot Water Generator Connections cont.
Hot Water Generator Startup
1. Make sure the power is off to the heat pump. Connect the wire
from the hot water generator pump to T1 on the contactor.
2. Close the drain valve to the water heater.
3. Open the cold water supply to the tank.
4. Open a hot water faucet in the building to bleed air from the
system. Close when full.
5. Open the pressure relief valve to bleed any remaining air from
the tank, then close.
6. If so equipped, turn the venting (burping) screw in the center of
the pump two (2) turns open (water will drip out), wait until all air is
purged from the pump, then tighten the plug. Use vent couplings to
bleed air from the lines.
7. Carefully inspect all plumbing for water leaks and correct
as required.
8. Before restoring electrical supply to the water heater, adjust the
temperature setting on the tank.
• On tanks with both upper and lower elements, the lower
element should be turned down to the lowest setting,
approximately 100°F. The upper element should be
adjusted to 120°F to 130°F. Depending upon the specific
needs of the customer, you may want to adjust the upper
element differently.
• On tanks with a single element, lower the thermostat
setting to 120°F.
9. After the thermostat(s) is adjusted, replace the access cover
and restore electrical supply to the water heater.
LX ULTRA SERIES INSTALLATION MANUAL
10. Make sure that any valves in the hot water generator circuit
are open.
11. Turn on the unit to heating.
12. The HWG pump should be running. When the pump is first
started, turn the venting (burping) screw (if equipped) in the
center of the pump two (2) turns open until water dribbles out,
then replace. Allow the pump to run for at least five minutes to
ensure that water has filled the circulator properly.
13. The temperature difference between the water entering
and leaving the hot water generator should be 5°F to 15°F.
The water flow should be approximately 0.4 gpm per ton of
nominal cooling.
14. Allow the unit to heat water for 15 to 20 minutes to be sure
operation is normal.
CAUTION: Never operate the HWG circulating
pump while dry. If the unit is placed in operation
before the hot water generator piping is connected,
be sure that the pump wires are disconnected from
the contactor.