Alarms, faults and system messages
9.4 List of alarms and faults
Number
Cause
F08501
Setpoint timeout
F08502
Monitoring time, sign-of-life ex-
pired
F08510
Send configuration data not valid •
A08511
Receive configuration data not
valid
A08526
No cyclic connection
A08565
Consistency error affecting ad-
justable parameters
F08700
Communications error
F13100
Know-how protection: Copy
protection error
F13101
Know-how protection: Copy
protection cannot be activated
350
Remedy
Check the PROFINET connection.
•
Set the controller to RUN mode.
•
If the error occurs repeatedly, check the monitoring time set (p2044).
•
Check the PROFINET connection.
•
Check the PROFINET configuration
Activate the controller with cyclic operation.
•
Check the parameters "Name of Station" and "IP of Station" (r61000,
•
r61001).
Check the following:
IP address, subnet mask or default gateway is not correct.
•
IP address or station name used twice in the network.
•
Station name contains invalid characters.
•
A CAN communications error has occurred. Check the following:
Bus cable
•
Baud rate (p8622)
•
Bit timing (p8623)
•
Master
•
Start the CAN controller manually with p8608 = 1 after the cause of the fault
has been resolved!
The know-how protection and the copy protection for the memory card are
active. An error occurred during checking of the memory card.
Insert a suitable memory card and switch the converter supply voltage
•
temporarily off and then on again (POWER ON).
Deactivate the copy protection (p7765).
•
Insert a valid memory card.
Operating Instructions, 07/2015, FW V4.7 SP3, A5E34263257B AC