Advertisement

Commissioning
5.3 Commissioning using a BOP-2 operator panel
9.
10.
11.
12.
13.
14.
15.
16.
You have entered all of the data that is necessary for the basic commissioning of your
inverter.
96
8.9.
Select the application:
VEC STD
PUMP FAN Speed-dependent load: Typical applications include
Select the default setting for the interfaces of the inverter that is suita-
ble for your application. You will find the available default settings in
Section: Default setting of the interfaces (Page 71)
Minimum and maximum motor speed
Motor ramp-up time
Motor ramp-down time
Ramp-down time for the OFF3 command
Complete the basic commissioning:
16.1. Switch over the display using an arrow key: nO → YES
16.2. Press the OK key.
Motor cooling
SELF
Natural cooling
FORCED
Forced-air cooling
LIQUID
Liquid cooling
NO FAN
Without fan
Constant load: Typical applications include belt conveyor
drives.
pumps and fans.
Operating Instructions, 07/2015, FW V4.7 SP3, A5E34263257B AC