Application class
Characteristics
•
•
•
•
Max. output fre-
quency
Commissioning
•
•
SINAMICS G120C converter
Operating Instructions, 07/2015, FW V4.7 SP3, A5E34263257B AC
Standard Drive Control
Typical settling time after a speed change:
100 ms ... 200 ms
Typical settling
time after after a
sudden load
change: 500 ms
Standard Drive
Control is suita-
ble for the follow-
ing requirements:
–
All motor
power ratings
–
Ramp-up time 0 → rated speed (depend-
ing on the motor power rating):
1 s (0.1 kW) ... 10 s (18.5 kW)
–
Applications with continuous load torque
without sudden load changes
Standard Drive Control is insensitive to inac-
curate motor data settings
550 Hz
Unlike "Dynamic Drive Control," no speed
controller needs to be set
As compared with "configuration for experts":
–
Simplified commissioning using prede-
fined motor data
–
Reduced number of parameters
5.4 Commissioning with a PC
Dynamic Drive Control
Typical settling time after a speed change:
•
< 100 ms
Typical settling time
•
after after a sudden
load change: 200ms
Dynamic Drive Con-
•
trol controls and lim-
its the motor torque
Typically achieves a
•
torque accuracy:
± 5 % for 15 % ...
100 % of the rated
speed
We recommend Dynamic Drive Control for the
•
following applications:
–
Motor power ratings > 11 kW
–
On sudden load changes 10% ... >100% of
the motor rated torque
Dynamic Drive Control is necessary for a ramp-
•
up time 0 → rated speed (depending on the mo-
tor power rating):
< 1 s (0.1 kW) ... < 10 s (18.5 kW).
240 Hz
Reduced number of parameters as compared
•
with "configuration for experts"
Commissioning
113