Troubleshooting: Heating Sequence of Operation (Continued)
CONTINUED
FIRST−STAGE (LOW FIRE) PRESSURE
SWITCH CLOSED WITHIN 2.5 MINUTES?
YES
15−SECOND COMBUSTION AIR INDUCER
PRE−PURGE INITIATED BY CLOSED FIRST−STAGE
PRESSURE SWITCH (or 15 SECOND
INTER−PURGE PERIOD.)
STATUS LED −− HEARTBEAT.
IGNITOR WARM−UP (20 SECONDS)
STATUS LED −− HEARTBEAT.
YES
IS IGNITOR INTACT AND CONNECTED?
YES
AT END OF IGNITOR 20 SECOND WARM UP
PERIOD, 4−SECOND TRIAL FOR IGNITION.
GAS VALVE OPENS, IGNITOR ENERGIZED DURING
4−SECOND TRIAL UNTIL FLAME SENSED.
YES
4−SECOND FLAME STABILIZATION PERIOD.
FLAME RECTIFICATION CURRENT CHECK
CAN FLAME BE PROVEN WITHIN 4
SECONDS AFTER GAS VALVE OPENS?
(u0.20 microamps)
FLAME PRESENT?
YES
CONTINUED ON NEXT PAGE
HEATING SEQUENCE OF OPERATION
NO
NO
COMBUSTION AIR INDUCER OFF, IGNITER OFF.
SIGNAL HOLDS UNTIL VOLTAGE RISES ABOVE 95
NO
IS 60−MINUTE RESET PERIOD COMPLETE?
NO
HAS CONTROL RESET IGNITION SEQUENCE
Page 46
THERMOSTAT CALLS FOR HEAT
STATUS LED − HEARTBEAT
(Refer to box A on previous page)
GAS VALVE OFF. COMBUSTION AIR INDUCER
OFF. INDOOR BLOWER OFF. UNIT WILL RETRY
AFTER 5−MINUTE WAIT PERIOD.
STATUS ERROR CODE 2 + 3.
COMBUSTION AIR INDUCER OFF, IGNITOR OFF.
SIGNAL HOLDS UNTIL IGNITOR IS REPLACED
OR RECONNECTED.
STATUS ERROR CODE 4 + 7.
IS VOLTAGE ABOVE 90 VOLTS?
NO
VOLTS. STATUS ERROR CODE 4 + 8.
GAS VALVE OFF. COMBUSTION AIR
INDUCER ON. INDOOR BLOWER OFF.
STATUS LED −− HEARTBEAT.
HAS CONTROL FAILED TO SENSE
FLAME FOR FIVE CONSECUTIVE TRIES
DURING A SINGLE HEAT DEMAND?
YES
WATCHGUARD MODE. GAS VALVE OFF,
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF.
STATUS ERROR CODE 4 + 1.
YES
FOUR (4) TIMES?
WATCHGUARD MODE.
STATUS ERROR CODE 4 + 3.
YES
NO
YES
NO