Pipe & Fittings Specifications - Lennox G61MPVT-36B-070 Installation Instructions Manual

Table of Contents

Advertisement

into the room. This reverse flow of the flue gas may result
in incomplete combustion and the formation of carbon
monoxide gas. This toxic gas might then be distributed
throughout the house by the furnace duct system.
Return air can be brought in through the bottom or either
side of the furnace. If a furnace with bottom return air is
installed on a platform, make an airtight seal between the
bottom of the furnace and the platform to ensure that the
unit operates properly and safely. Use fiberglass sealing
strips, caulking, or equivalent sealing method between the
plenum and the furnace cabinet to ensure a tight seal. If a
filter is installed, size the return air duct to fit the filter frame.
Pipe & Fittings Specifications
All pipe and fittings to be Pressure Pipe, Class E /
Class 12 / Schedule 40 or equivalent
All pipe, fittings, primer and solvent cement must conform
OUTDOOR TERMINATION KITS AND CORRESPONDING EQUIVALENCIES
Outdoor Ex-
haust Accel-
VENT
erator
PIPE
UNIT
DIA.
(Dia. X
MODEL
(in.)
Length)
40mm X
305mm
50mm
1.2
80mm
2.4
−070
100mm
4.3
Not
50mm
Allowed
Not
80mm
−090
Allowed
Not
100mm
Allowed
Not
80mm
Allowed
−110
Not
100mm
Allowed
Not
80mm
Allowed
−135
Not
100mm
Allowed
*Requires field−provided and installed 40mm exhaust
accelerator.
TABLE 4
Vent Pipe Length Equivalency (meters)
Outdoor Ex-
40mm
haust Accel-
(1−1/2")
erator
Concentric
(Dia. X
Kit
Length)
50mm X
71M80
305mm
Not
3.6
Allowed
Not
7.3
Allowed
Not
12.8
Allowed
Not
0.3
Allowed
Not
0.6
Allowed
Not
1.2
Allowed
Not
0.6
Allowed
Not
1.2
Allowed
Not
1.8
Allowed
Not
3.0
Allowed
Page 10
with Australian standards. The solvent shall be free flow-
ing and contain no lumps, undissolved particles or any for-
eign matter that adversely affects the joint strength or
chemical resistance of the cement. The cement shall
show no gelation, stratification, or separation that cannot
be removed by stirring.
Solvent cements for plastic pipe are flammable liq-
uids and should be kept away from all sources of
ignition. Do not use excessive amounts of solvent
cement when making joints. Good ventilation should
be maintained to reduce fire hazard and to minimize
breathing of solvent vapors. Avoid contact of cement
with skin and eyes.
Table 4 lists the available exhaust termination kits, as well
as vent pipe equivalencies which must be used when sizing
vent pipe. All Lennox vent terminations are PVC or ABS.
50mm (2")
80mm (3")
50mm (2")
Concentric
Concentric
Kit
Kit
60M29
60L46
Not
Not
Allowed
Allowed
Not
Not
Allowed
Allowed
Not
Not
Allowed
Allowed
.9
.9
1.8
1.8
3.7
3.7
1.8
1.8
3.7
3.7
Not
4.6
Allowed
Not
7.6
Allowed
**Requires field−provided and installed 50mm exhaust
accelerator.
CAUTION
80mm (3")
Wall Plate
Wall Plate
Kit
Kit
22G44
44J40
1.2
1.2*
2.4
2.4*
4.3
4.3*
Not
0.3
Allowed
Not
0.6
Allowed
Not
1.2
Allowed
Not
0.6
Allowed
Not
1.2
Allowed
Not
1.8
Allowed
Not
3.0
Allowed
50mm (2")
Wall Ring
Kit
15F74
1.2
2.4
4.3
0.3**
0.6**
1.2**
0.6
1.2
Not
Allowed
Not
Allowed