Lennox G61MPV Engineering Data

Lennox G61MPV Engineering Data

Dave lennox signature collection multi−position − two−stage heat − variable speed blower gas furnaces
Hide thumbs Also See for G61MPV:

Advertisement

E N G I N E E R I N G D A T A
MODEL NUMBER IDENTIFICATION
G = Gas Furnace
61 = Two−Stage 90% Minimum AFUE
MP = Multi−Position
V = Variable Speed Blower Motor
Nominal Add−On Cooling Capacity
Multi−Position − Two−Stage Heat − Variable Speed Blower
G 61
MP
Unit Type
Series
Configuration
Blower
36 = 2−3.5 tons
60 = 4−5 tons
DAVE LENNOX SIGNATURE
Input − 44,000 to 132,000 Btuh
Nominal Add−on Cooling − 2 to 5 Tons
V
36
B 070
1
Cabinet Width
B = 17−1/2 in.
C = 21 in.
D = 24−1/2 in.
1
Indoor coils with the same letter designation will physically match the furnace.
G A S F U R N A C E S
G61MPV
®
COLLECTION
Bulletin No. 210390
February 2007
Supersedes December 2006
AFUE − up to 95.0%
Nominal Gas Heat Input
045 = 45,000 Btuh
070 = 66,000 Btuh
071 = 66,000 Btuh (95% AFUE)
090 = 88,000 Btuh
091 = 88,000 Btuh (95% AFUE)
110 = 110,000 Btuh
111 = 110,000 Btuh (95% AFUE)
135 = 132,000 Btuh

Advertisement

loading

Summary of Contents for Lennox G61MPV

  • Page 1 G A S F U R N A C E S G61MPV DAVE LENNOX SIGNATURE ® COLLECTION Multi−Position − Two−Stage Heat − Variable Speed Blower E N G I N E E R I N G D A T A Bulletin No.
  • Page 2 Kits. control panel must be able to interface and communicate CSA certified. with the variable speed blower motor in the unit. Lennox Termination Kits − Wall Assembly Harmony IIIt Zone Control Panel has this capability. Close Couple − Direct Vent Applications Only 2 or 3 inch kit consists of close-couple, side-by-side PVC DIRECT VENT / NON−DIRECT VENT...
  • Page 3 Cemented to steatite block for protection against current ® Lennox Duralok Plus Heat Exchanger Assembly leakage. Lennox developed heat exchanger assembly consists of Ignition leads constructed of nickel plated copper primary heat exchanger and secondary condenser coil enclosed in high temperature Teflon insulation for assembly.
  • Page 4 Electronic flame sensor assures safe, reliable operation. Should flame fail to ignite, flame sensor will initiate 4 re−attempts at ignition before locking out unit operation for 60 minutes. G61MPV / Page 4...
  • Page 5 66 ft. length, 1/2 in. wide fiberglass. Thermostat 60 ft. length, 2 in. wide aluminum foil. See Thermostat bulletins in Controls section and Lennox Condensate Trap Alternate Location Kit Price Book for a complete list of thermostats. Allows condensate drain to be installed on the opposite CABINET side of the furnace from the exhaust venting (up−flow...
  • Page 6: Specifications

    NOTE − Filters and provisions for mounting are not furnished and must be field provided. Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non−weatherized furnaces. G61MPV / Page 6...
  • Page 7 56M22 56M22 56M23 59M13 59M14 59M87 59M87 −135 59M17 − − − 56M93 56M93 59M13 59M14 59M87 59M87 High Altitude Orifice Kit is required and must be ordered separately for applications from 7501 to 10,000 ft. G61MPV / Page 7...
  • Page 8 Requires field provided 2 in. outdoor exhaust accelerator. For use only in non−direct vent applications, when snow riser is not required. Requires field provided 2 in. outdoor exhaust accelerator. Outdoor exhause accelerator included in 71M80 kir; for use with −045−070−071 models. G61MPV / Page 8...
  • Page 9: Installation Configurations

    National Standard of Canada CAN/CGA-149.1 and .2. Allow proper clearances to accommodate condensate trap and vent pipe installation. Do not install the furnace directly on carpeting, tile, or other combustible materials other than wood flooring. G61MPV / Page 9...
  • Page 10 (597) 4−1/4 3/4 (19) Bottom Return Bottom Return (108) Air Opening Air Opening FRONT VIEW SIDE VIEW Model No Model No. G61MPV−36B−045 G61MPV−36B−070 17−1/2 16−3/8 G61MPV−36B−071 G61MPV−36C−090 G61MPV−60C−090 G61MPV−60C−091 19−7/8 19−1/2 G61MPV−60C−110 G61MPV−60C−111 G61MPV−60D−135 24−1/2 23−3/8 G61MPV / Page 10...
  • Page 11 533 23−5/8 600 53−5/8 1362 CR33-60D−F 24−1/2 622 24−1/2 622 23−5/8 600 53−5/8 1362 (1016) HORIZONTAL POSITION Model Model Number CH33−42B−2F CH33−36B−2F CH33−48C−2F 26−1/2 673 66−1/2 1689 CH33−36C−2F CH33−60D−2F CH33−44/48B−2F CH33−62D−2F 31−1/2 800 71−1/2 1816 CH33−50/60C−2F G61MPV / Page 11...
  • Page 12 Front Of Furnace 1-1/2 (38) TOP VIEW SIDE VIEW DOWN-FLOW Model No Model No. ADDITIVE FLOOR BASE G61MPV−36B−045 G61MPV−36B−070 19−9/16 16−9/16 18−3/4 G61MPV−36B−071 FLOOR G61MPV−36C−090 OPENING G61MPV−60C−090 G61MPV−60C−091 23−1/16 20−1/16 22−1/4 G61MPV−60C−110 (559) G61MPV−60C−111 G61MPV−60D−135 26−9/16 23−9/16 25−3/4 G61MPV / Page 12...
  • Page 13 33−3/8 (848) − 71M80/69M29 38−7/8 (987) − 60L46 6−1/2 (165) (152) EXHAUST 3−1/2 (89) − 71M80/69M29 4−1/2 (114) − 60L46 INTAKE AIR Outdoor Exhaust Accelerator TERMINATION ELBOW ASSEMBLY included with 71M80 (Field Supplied) (Furnished) (Required with −045−070 models) G61MPV / Page 13...
  • Page 14 É É É É É É É É É É É É É É É É É É É É É É É É É É É É É É É É É É É É É É É É É É É G61MPV / Page 14...
  • Page 15 É É É É É É É É É É É É É É É É É É É É É É É É É É É É É É É É É É É É É É É É G61MPV / Page 15...
  • Page 16: Blower Data

    First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm. Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 442 cfm. G61MPV−36B−045 BLOWER MOTOR WATTS Motor Watts @ Various External Static Pressures −...
  • Page 17 First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm. Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 458 cfm. G61MPV−36B−070 BLOWER MOTOR WATTS Motor Watts @ Various External Static Pressures −...
  • Page 18 First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm. Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 458 cfm. G61MPV−36B−071 BLOWER MOTOR WATTS Motor Watts @ Various External Static Pressures −...
  • Page 19 First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm. Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 479 cfm. G61MPV−36C−090 BLOWER MOTOR WATTS Motor Watts @ Various External Static Pressures −...
  • Page 20 First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm. Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 449 cfm. G61MPV−60C−090 BLOWER MOTOR WATTS Motor Watts @ Various External Static Pressures −...
  • Page 21 First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm. Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 449 cfm. G61MPV−60C−090 BLOWER MOTOR WATTS Motor Watts @ Various External Static Pressures −...
  • Page 22 First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm. Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 449 cfm. G61MPV−60C−090 BLOWER MOTOR WATTS Motor Watts @ Various External Static Pressures −...
  • Page 23 First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm. Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 458 cfm. G61MPV−60C−091 BLOWER MOTOR WATTS Motor Watts @ Various External Static Pressures −...
  • Page 24 First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm. Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 458 cfm. G61MPV−60C−091 BLOWER MOTOR WATTS Motor Watts @ Various External Static Pressures −...
  • Page 25 First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm. Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 458 cfm. G61MPV−60C−091 BLOWER MOTOR WATTS Motor Watts @ Various External Static Pressures −...
  • Page 26 First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm. Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 463 cfm. G61MPV−60C−110 BLOWER MOTOR WATTS Motor Watts @ Various External Static Pressures −...
  • Page 27 First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm. Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 463 cfm. G61MPV−60C−110 BLOWER MOTOR WATTS Motor Watts @ Various External Static Pressures −...
  • Page 28 First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm. Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 463 cfm. G61MPV−60C−110 BLOWER MOTOR WATTS Motor Watts @ Various External Static Pressures −...
  • Page 29 First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm. Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 458 cfm. G61MPV−60C−111 BLOWER MOTOR WATTS Motor Watts @ Various External Static Pressures −...
  • Page 30 First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm. Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 458 cfm. G61MPV−60C−111 BLOWER MOTOR WATTS Motor Watts @ Various External Static Pressures −...
  • Page 31 First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm. Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 458 cfm. G61MPV−60C−111 BLOWER MOTOR WATTS Motor Watts @ Various External Static Pressures −...
  • Page 32 First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm. Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 470 cfm. G61MPV−60D−135 BLOWER MOTOR WATTS Motor Watts @ Various External Static Pressures −...
  • Page 33 First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm. Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 470 cfm. G61MPV−60D−135 BLOWER MOTOR WATTS Motor Watts @ Various External Static Pressures −...
  • Page 34 First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm. Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 470 cfm. G61MPV−60D−135 BLOWER MOTOR WATTS Motor Watts @ Various External Static Pressures −...
  • Page 36 Contact us at 1−800−4−LENNOX NOTE − Due to Lennox’ ongoing committment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.