Siemens OP5 Equipment Manual page 139

Operator panel
Table of Contents

Advertisement

Message
Cause
$ 303
PLC did not invert life flag. Data
have not been requested or are no
longer valid
$ 304
Invalid job number or job parame-
ters
$ 305
Data block number x missing
$ 306
Temporary driver error
$ 307
Counter x not present on PLC
$ 308
Timer x not present on PLC
$ 309
Input x not present on PLC
$ 310
Output x not present on PLC
$ 311
Flag x not present on PLC
$ 312
Print job rejected because similar
job now being executed
$ 313
Print job will be processed later be-
cause printer now busy
$ 315
Information text has not been con-
figured for highlighted object (e.g.
message, variable)
$ 316
Current password level too low for
$ 317
required operator input
$ 318
Login attempted with invalid pass-
word
$ 319
You entered and tried to edit an ex-
isting password
$ 320
$ 321
$ 322
$ 323
In a buffer mask, you pressed
(message text), though an
entry does not exist for the current
message.
$ 324
The screen number or entry number
in your input does not exist
Manual OP5, OP15
( ) J31069-D0840-U001-A2-7618
System Messages
Action
Check PLC status
Modify job on PLC
Create the data block that is missing
Modify configuration
(variable)
Modify configuration
(variable)
Modify configuration
(variable)
Modify configuration
(variable)
Modify configuration
(variable)
Wait until previous job terminated; initiate
again
Log in at higher password level
Enter password first, and then specify level
Password must contain at least 3 characters
B-5