Omron CJ1W-ETN11 Operation Manual page 134

Sysmac cs/cj series ethernet units
Hide thumbs Also See for CJ1W-ETN11:
Table of Contents

Advertisement

Using Socket Services with Socket Service Request Switches
CPU Unit
Socket Service
Request Switches
Socket Service
Parameters
An illustration of using Socket Service Request Switches to execute socket
services is provided below.
CS/CJ-series PC
Ethernet Unit
Refreshed
(See note 1.)
Refreshed
(See note 2.)
Note
1. Socket Service Request Switches in the CPU Bus Unit Area in the CIO
Area are used to send a service request from the CPU Unit to the Ethernet
Unit.
2. The Socket Service Parameters in the CPU Bus Unit Area in the DM Area
are used to specify the service being requested from the Ethernet Unit.
The CPU Bus Unit Area in the DM Area is also used to receive results of
processing from the Ethernet Unit to the CPU Unit.
After setting the required parameters in a Socket Service Parameter Area in
the CPU Bus Unit Area in the DM Area, the Socket Service Request Switches
can be used to request opening, sending, receiving, or closing for either the
UDP or TCP protocol. When requesting a send, send data at the send/receive
data addresses set in the parameter area is sent. When requesting a recep-
tion, data is received to the send/receive data addresses set in the parameter
area.
Host computer or other device
TCP data
transfers
System
call
UDP data
transfers
Section 6-2
User program
113