Troubleshooting Procedures; Startup Problems - Omron CJ1W-ETN11 Operation Manual

Sysmac cs/cj series ethernet units
Hide thumbs Also See for CJ1W-ETN11:
Table of Contents

Advertisement

Troubleshooting Procedures

Error
Meaning
code
0300
Parameter error; packet discarded Commands
0601
CPU Bus Unit error
0602
CPU Bus Unit memory error

10-5 Troubleshooting Procedures

10-5-1 Startup Problems

1,2,3...
Detailed error code
1st byte
Bit 15:
Bits 08 to 14: SNA
Bits 00 to 07: SA1
Responses
Bit 15:
Bits 08 to 14: DNA
Bits 00 to 07: DA1
Arbitrary
01: Read
error
02: Write
error
Note
1. The time information in the CPU Unit is used in the CPU Bus Units.
2. If the time information cannot be read from the CPU Unit, the time stamp
in the error log will be all zeros. This can occur due to CPU Unit startup
error, unit number errors, CPU error, and model number errors. If the time
is read out from a Programming Device, the time will be shown as all zeros
in the year 2000.
3. The battery must be installed in the CS/CJ-series CPU Unit, the power
turned ON, and then the time set before the clock in the CPU Unit can be
used. The time will not be set correctly in the error log unless the clock time
is set correctly.
4. An error record is not created in EEPROM when a CPU Bus Unit memory
error occurs.
The following procedures can be used to troubleshoot various problems in
system operation.
Most of the initial steps in these procedures are in question form. Continue in
sequence until a "True" answer tells you to jump to a specified step or until you
are told to perform a specific action that corrects the problem. If performing
the action does not correct the problem, return to the beginning of the proce-
dure and start over.
1. RUN indicator lit?
True ➨ Step 14.
2. ERH indicator lit?
True ➨ Step 12.
3. ERC indicator lit?
True ➨ Step 9.
4. Power not supplied to CPU Unit?
True ➨ Make sure that sufficient power is supplied to the CPU Unit.
5. Ethernet Unit loose on Rack?
2nd byte
Check the command format and
OFF
set the correct command data.
ON
Restart the CPU Unit. If the prob-
lem persists, replace the Ethernet
Unit.
06: Error log
Restart the CPU Unit. If the prob-
lem persists, replace the Ethernet
Unit.
Section 10-5
Correction
PROM
---
Saved
Saved
(except
for error
log)
EE-
197

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cs1w-etn11Cs/cj seriesCs1w-etn01W343-e1-07