Internode Echo Test - Omron CJ1W-ETN11 Operation Manual

Sysmac cs/cj series ethernet units
Hide thumbs Also See for CJ1W-ETN11:
Table of Contents

Advertisement

Command/Response Reference
Total Number of Packets
Received (Response)
Total Number of Receive
Errors (Response)
Total Number of Packets
Sent (Response)
Total Number of Errors
Sent (Response)
Total Number of Send
Collisions
Precautions
Response Codes

11-3-4 INTERNODE ECHO TEST

Command Block
Response Block
Parameters
Test Data (Command,
Response)
Precautions
220
Note If this bit turns ON for the CS1W-ETN11 or CJ1W-ETN11, the Ether-
net Unit has malfunctioned.
Address Mismatch
The address conversion method was set for automatic generation, but the
node number and the last byte of the local IP address do not agree, or other
host sections are 0.
EEPROM Error
An error occurred in the EEPROM memory in the Ethernet Unit.
The total number of packets received by the Ethernet Unit is returned.
The total number of errors detected while the Ethernet Unit was receiving is
returned. The types of error detected are short packet errors, alignment
errors, and CRC errors.
The total number of packets sent by the Ethernet Unit is returned.
The total number of packet errors detected while the Ethernet Unit was send-
ing is returned.
The number of packets damaged by 16 collisions with data from other nodes
during Ethernet Unit transmissions.
Counting of the total number of packets received, total number of receive
errors, total number of packets sent, total number of errors sent, and total
number of send collisions is discontinued when the counted value reaches the
maximum value.
Response code
0000
Normal
1001
Command too large
Runs the echo test between specified nodes.
08
01
1,998 bytes max.
Command
code
08
01
Command
Response
code
code
This command specifies the data to be sent to the specified nodes. Up to
1,998 bytes can be specified. The response sends back data identical to the
data specified in the command. An abnormality is assumed if the data
returned in the response differs from the test data sent.
The test destination node is the destination node specified in the CMND(194)
instruction operands.
Description
Test data
1,998 bytes max.
Test data
Section 11-3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cs1w-etn11Cs/cj seriesCs1w-etn01W343-e1-07

Table of Contents