Ip Address Table Read - Omron CJ1W-ETN11 Operation Manual

Sysmac cs/cj series ethernet units
Hide thumbs Also See for CJ1W-ETN11:
Table of Contents

Advertisement

Command/Response Reference

11-3-21 IP ADDRESS TABLE READ

Command Block
Response Block
Parameters
Number of Records
(Command, Response)
Maximum Number of
Stored Records
(Response)
Number of Stored
Records (Response)
IP Address Table Records
(Response)
Precautions
Response Codes
Reads the IP address table.
27
60
Command
Number of
code
records
27
60
Command
Response
Maximum
code
code
number
of stored
records
The number of records to read is specified between 0000 and 0020 (0 to 32
decimal) in the command. If this value is set to 0, the number of stored
records is returned but the IP address table records are not returned. The
response returns the actual number of records read.
The maximum number of records that can be stored in the IP address table is
returned. The maximum number of stored records is fixed at 32.
The number of IP address table records stored at the time the command is
executed is returned as a hexadecimal number.
The number of IP address table records specified in the number of records
parameter is returned. The total number of bytes in the IP address table
records is calculated as the number of records x 6 bytes/record. The configu-
ration of the 6 bytes of data in each record is as shown in the following dia-
gram.
1
FINS Node Number
Node number for communications via the FINS command.
IP Address
IP number used by TCP/IP protocol.
If the IP address table contains fewer records than the number specified in the
number of records parameter, all the records contained in the IP address table
when the command is executed will be returned and the command execution
will end normally.
An error response will be returned if the IP address conversion method in the
system mode settings is set to the automatic generation method.
Response code
0000
Normal
1001
Command too large
1002
Command too small
2307
IP address conversion method is set to the automatic genera-
tion method.
Number
Number
of
of
stored
records
records
00
FINS node
IP address
number
Description
Section 11-3
6 bytes
6 bytes
IP address
IP address
table records
table records
6 bytes
239

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cs1w-etn11Cs/cj seriesCs1w-etn01W343-e1-07

Table of Contents