Using Socket Services with Socket Service Request Switches
TCP Socket Close Request
6-2-3

Socket Service Request Switches

122
Response
code
110C
Request Switch turned ON during other processing.
220F
Specified socket is already processing a send request.
2210
The specified socket is not open.
2211
Unit is busy; cannot execute.
2607
Specified Socket Service Parameter Area is already being used for
another socket.
0020
Connection with remote socket broken during send (EPIPE).
003E
Internal buffer cannot be obtained due to high reception traffic
(ENOBUFS).
0042
The remote IP address is a broadcast address and the number of
(See note.)
bytes to send is greater than 1,472 bytes (EMSGSIZE).
0044
ICMP data received (ENOPROTOOPT).
(See note.)
0045
Error in communications with remote node (ECONNABORTED).
(See note.)
004A
Error in communications with remote node (ECONNREFUSED)
(See note.)
004B
Error in communications with remote node (ECONNREFUSED)
(See note.)
004E
Remote IP address parameter error (ENETUNREACH).
(See note.)
004F
ICMP data received (EHOSTDOWN).
(See note.)
0051
Remote IP address parameter error (EHOSTUNREACH).
(See note.)
0053
Error in communications with remote node (ETIMEDOUT).
(See note.)
0081
The specified socket was closed during send processing.
Note These response codes will be returned only on large, multilevel networks.
Response
code
0000
Normal end
2210
The specified socket is not open.
2211
Unit is busy; cannot execute.
2607
Specified Socket Service Parameter Area is already being used for
another socket.
0302
CPU Unit error; cannot execute.
Socket Service Request Switches are manipulated to request socket ser-
vices. These bits are called Socket Service Request Switches, and are turned
ON in the CPU Unit to request socket services through the Ethernet Unit.
The Socket Service Request Switches are allocated in the CPU Bus Unit Area
in the CPU Area starting at the word n+ 19. The value of n can be calculated
from the unit number as follows: