Installation
 Connect the syphon hose (fig. 15, item 3) and the
rubber sleeve (fig. 15, item 2) to the syphon (fig. 15,
item 1).
5.6

Connecting the condensate drain pipe

 Connect the condensate drain pipe to the syphon.
Observe the following regulations:
– The waste water disposal regulations.
– Plastic pipework must be used to drain the
condensate, at least until it is delivered to the
seweage system.
– The condensate must be able to run into a funnel
(or neutralisation tank) without restrictions.
This prevents condensate from building up in the
boiler. The syphon in the connection kit must no be
permanently connected to the condensate drain
pipe. The minimum distance between the syphon
and the condensate drainage pipe is 2 cm (fig. 16,
item 1).
5.7

Connecting the expansion vessel (accessory)

DAMAGE TO THE UNIT
due to faulty pressure relief valve.
 The expansion vessel must be of suffi-
cient capacity.
14
pump group Logamax plus GB162-65/80/100 - Subject to modifications resulting from technical improvements!