CVX 600 Hardware Installation Guide
Connecting Alarms

Procedure

To connect alarms to the terminal block, follow these steps:
Step
1
2
3
4
5
2-6
Action
Select the terminals you want to use for the audible or visual alarm.
Use a small flat-tip screwdriver to loosen the two terminal screws for each
alarm device you want to connect. For example, if you want to connect an
audible alarm for a critical condition, loosen the terminal screws for the
terminals labeled Crit(ical) and Ret(urn).
Remove 1/2 inch
of wire insulation.
Connect wires
to alarm device.
Use a wire stripper to remove approximately 1/2 inch of insulation from the
wires.
Insert the wires into the terminals and tighten the screws to 1 to 2 in-lb using a
1/16-inch flat-tip screwdriver.
Connect the other end of the wires to the alarm device.
SCC-RLTM
Tighten screws to
1 to 2 in-lb, using a
1/16-inch flat-tip
screwdriver.
Optical SCC-II-LTM
296-1011-202 Rel. 5.0, Doc. Rev. 02.01
CVX-0184C