Installing the CVX 600 Chassis

Mounting the Chassis in a Rack

The mounting flanges are preinstalled on the chassis.
1-20
Caution: Nortel Networks recommends using a PTE 2000 rack. Nortel
Networks does not authorize the use of racks with front or rear doors or
side panels. The operating environment must provide airflow at 200 cubic
feet per minute (CFM) per CVX 600 chassis at a temperature range of 32°
to 104°F (0° to 40°C). The optimal ambient temperature for reliable
CVX 600 operation is 68° to 77°F (20° to 25°C).
Caution: Before you install the CVX 600 chassis in a rack, ensure that
the rack is sturdy and well secured. A fully configured CVX 600 chassis
weighs about 70 lb, which could make an unsecured rack top-heavy or
unstable.