Parallel Installation; Corner Installation; Wall And Ceiling Clearances; Hearth Requirements - Vermont Castings SDDVTBSSB Installation And Operating Instructions Manual

Sddvt series stardance direct vent gas heater
Hide thumbs Also See for SDDVTBSSB:
Table of Contents

Advertisement

Stardance
Direct Vent Gas Heater
®

PARALLEL INSTALLATION

Minimum Clearance and Flue Centerline
C
D
C L
B
Stove Clearances:
Pipe Centerlines:
ST128b
Stardance
Figure 3 Parallel installation, minimum back and side
clearances, and flue centerlines.
flue centerline
9/28/00 djt

CORNER INSTALLATION

Minimum Clearance and Flue Centerline
B
B
A
Stove Clearance:
Pipe Centerline:
Figure 4 Corner installation, minimum corner clearances and
ST129b
flue centerline.
Stardance
corner specs
9/28/00 djt
20306760
C L
A: 4" (102 mm)
B: 4" (102 mm)
C: 15
" (395 mm)
1
2
D: 9" (229 mm)
A
A: 4" (102 mm)
B: 14
" (370 mm)
1
2
Wall Centerline from Floor
Direct Vent Only
A
Effective Minimum
Wall Thimble
Centerline
Figure 5 Minimum wall centerline.

WALL AND CEILING CLEARANCES

Direct Vent Only
A: Rear Wall
B: Min. Clearance
C: Min. Alcove Height
D: Max. Alcove Depth
Sidewall Clearance
* needed for installing DuraVent Minimum Vent Kit #2792 or
HHT Minimum Vent Kit #SLP-FSSK.
Figure 6 Dimensions and clearances to ceiling or alcove.

HEARTH REQUIREMENTS

The Stardance heater must be installed on rigid flooring.
When the heater is installed directly on any combustible
surface other than wood flooring, a metal or wood panel
extending the full width and depth of the unit must be used
as the hearth. There are no other hearth requirements.
PRE-INSTALLATION
A
56" (1480 mm) (HHT Pipe)
52" (1378 mm) (DuraVent Pipe)
ST131b
Stardance
wall thimble
9/28/00 djt
D
B
C
4" (102 mm)
45
" (1154 mm)*
1
ST101b
4
72" (1830 mm)
Stardance
48" (1220 mm)
Direct Vent
4" (102 mm)
Min. Clrnc
9/28/00 djt
A
7