Table 6: Accessories (Order Separately) (Part 2 of 2)
Code Number
Description
2
Outside Air Temperature Sensor
TE-6363P-1
TEC20-A-1
Replacement Antenna for TEC20 Coordinator
3
Remote Antenna for TEC20 Coordinator
TEC20-RA-1
4
DIN Rail Mount 24 VAC/DC Power Module for TEC20 Coordinator
NPB-PWR
TEC20-8X-1
120 VAC to 15 VDC Power Supply for TEC20 Coordinator
TEC20-9B-1
Replacement Battery Pack for TEC20 Coordinator
1.
The TEC-3-PIR Accessory Cover can be used to replace the existing cover on a non-PIR TEC2001-4 Thermostat
Controller to provide occupancy sensing capability.
2.
Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available; refer to the
TE-6300 Series Temperature Sensors Product Bulletin (LIT-216320) for more details.
3.
This antenna is used when the TEC Coordinator is installed inside a metal cabinet, or when a remote antenna is required by
physical installation.
4.
DIN Rail: Type NS35/7.5 (35 x 7.5 mm) and DIN rail end clips. Length of DIN rail depends on the number of DIN rail
mounted options.

Technical Specifications

TEC2001-4 and TEC2001-4+PIR Single-Stage Wireless Thermostat Controllers (Part 1 of 2)
Power Requirements
Relay/Triac Contact Rating
Relay/Triac Contact Rating
Digital Inputs
Analog Inputs
Wire Size
Transmission Range
RF Band
Transmission Power
Temperature Range
Temperature Sensor Type
Resolution
Control Accuracy
Auxiliary/Outdoor Air
Temperature Indication Range
Minimum Deadband
Ambient Conditions
TEC2001-4 and TEC2001-4+PIR Single-Stage Wireless Thermostat Controllers Installation Instructions
19 to 30 VAC, 50/60 Hz, 2 VA (Terminals RC and C) at 24 VAC Nominal, Class 2 or
Safety Extra-Low Voltage (SELV)
19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush, Class 2 or SELV
On/Off and Floating Control: 19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum,
3.0 A In-Rush, Class 2 or SELV
Voltage-Free Contacts across Terminal C to Terminals DI1 and DI2
Resistive Inputs (RS and UI3) for 10k ohm Johnson Controls Type II Negative
Temperature Coefficient (NTC) Thermistor Sensors
18 AWG Maximum, 22 AWG Recommended
Through Walls: 10 m (30 ft)
Line-of-Sight (Open Space): 30 m (100 ft)
Direct-Sequence Spread-Spectrum Transmission; 2.4 Ghz unlicensed band
10 mW Maximum
Backlit Display: -40.0°C/ -40.0°F to 50.0°C/122.0°F
Heating Control: 4.5°C/40.0°F to 32.0°C/90.0°F in 0.5° Increments
Cooling Control: 12.0°C/54.0°F to 100.0°F/38.0°C in 0.5° Increments
Local 10k ohm Negative Temperature Coefficient (NTC) Thermistor
±0.1C°/±0.2F°
±0.5C°/±0.9F° at 21.0°C/70.0°F Typical Calibrated
-40.0°C/-40.0°F to 50.0°C/122.0°F
1C°/2F° between Heating and Cooling
Operating: 0 to 50°C (32 to 122°F); 95% RH Maximum, Noncondensing
Storage: -30 to 50°C (-22 to 122°F); 95% RH Maximum, Noncondensing
15