Wiring
CAUTION: Risk of Electric Shock.
!
Disconnect the power supply before
making electrical connections to avoid
electric shock.
CAUTION: Risk of Property Damage.
!
Do not apply power to the system before
checking all wiring connections. Short
circuited or improperly connected wires
may result in permanent damage to the
equipment.
IMPORTANT: Make all wiring connections in
accordance with local, national, and regional
regulations. Do not exceed the electrical ratings of
the thermostat controller.
When replacing an existing thermostat controller,
remove and label the wires to identify the terminal
functions. When replacing a thermostat controller of the
same model, simply remove the old screw terminal
blocks and reinsert them onto the PCB of the
replacement thermostat controller.
Terminal
Energizes on Call for Heating
W1
Energizes on Call for Cooling
Y1
G
Energizes Fan in Accordance with the Selected Fan Mode
24 VAC from Equipment Transformer
RC
24 VAC (Common from Equipment Transformer
C
24 VAC for Heating Stage
RH
Auxiliary Output
Aux
Configurable Digital Input 1
DI1
Configurable Digital Input 2
DI2
Remote Room Sensor
RS
Sensor Common
Scom
Auxiliary/Outdoor Air Sensor
OS
Remote Monitoring Supply Temperature Sensor
MS
G
Y1
RC
Fan
Cool 1
24 VAC
Thermostat Power
Figure 5: Wiring the TEC2001-4 or TEC2001-4+PIR Thermostat Controller
4
TEC2001-4 and TEC2001-4+PIR Single-Stage Wireless Thermostat Controllers Installation Instructions
Function
)
Aux
C
RH
W1
Heat 1
Aux
If using the same power source
for the thermostat and heating loads,
install a jumper across RC and RH.
To wire the thermostat controller:
1. Strip the ends of each wire 6 mm (1/4 in.) and
connect them to the appropriate screw terminals as
indicated in Figure 5.
Note: If multiple wires are inserted into the screw
terminals, be sure to properly twist the wires
together prior to inserting them into the screw
terminals.
2. Carefully push any excess wire back into the wall.
Note: Seal the hole in the wall with fireproof
material to prevent drafts from affecting the
ambient temperature readings.
3. Reinsert the screw terminal blocks onto the PCB.
4. Reattach the cover to the mounting base (top side
first).
5. Use a Phillips-head screwdriver to reinstall the
security screw on the bottom of the thermostat
controller cover.
See Figure 5 for information on wiring the thermostat
controller.
Four-Pole
Left Top Connector
Y1
Seven-Pole Bottom Connector
Aux
Aux Contact (High Side Common)
• Lighting
• On/Off Actuation
• Exhaust Fan
DI1
RS
DI2
Scom
Remote
Room
Sensor
Two-Pole
Right Top
Connector
G
RC
C
RH W1
OS
DI1 DI2 RS
Scom
MS
OS
MS
Remote
Auxiliary/
Monitoring
Outdoor
Supply
Air Sensor
Temperature
Sensor